EDAC 222-02 AUTO ALARM DIALLER
- 25 -
Function F06 Answer Incoming Calls When no Inputs Active (Idle)
You may wish to periodically dial into the EDAC 222-02 to confirm that it is in idle state. This can
be useful if you have previously received a notification call of an alarm which may cancel itself e.g.
electrical power will be automatically restored after a power failure. Because the alarm condition is
removed, the EDAC 222-02 will reset itself to the idle state.
The EDAC 222-02 will use this value only when there are no Inputs active and the EDAC 222-02 is
in the idle state.
NOTE: Do not use one ring.
06
Answer all calls after …
2
to
9
= 2 to 9 rings,.
#
= 12 rings when idle.
0
= Never answer any incoming
calls when idle
Default: 4 (Answer calls after four rings)
NOTE:
If using Outputs, or remote modem configuration, you will need to consider
appropriate values for functions
F04, F05
and
F06
, to ensure the EDAC 222-02
answers the phone appropriately.
For installations that only use voice alarm notification calls where no user call back is required,
functions
F04, F05
and
F06
can be set to zero ensuring the EDAC 222-02 will never answer an
incoming alarm call. This allows the phone line to be used for other day-to-day activities. This
configuration requires that the operator acknowledges the alarm notification call on the phone they
receive the alarm notification call on.