OPTIONAL DIRECT EXHAUST SYSTEM
The optional FDVS is to be used in conjunction
with the PF boiler for indoor installations requiring
through the wall venting. The FDVS is designed
as an integral part of the PF boiler, eliminating the
need for a power venter.
Oil boiler FDVS kits include an oil burner with
adjustable post purge timer and solenoid valve.
For through the wall venting, this post purge burner
must be used in place of the standard burner that is
furnished with the boiler.
SELECTION OF BOILER SIZE
Selection of boiler size should be based upon “Net
I=B+R Rating MBH being equal to or greater than
the calculated heat loss of the building.
These boilers are low pressure sectional cast
iron boilers constructed and hydrostatically tested
for a maximum working pressure of 50 psi in
accordance with A.S.M.E. (American Society of
Mechanical Engineers) Section IV Standards for
cast iron heating boilers. They are capacity rated
in accordance with the code of the Hydronics
Institute.
These boilers operate on #2 Heating Oil, Natural
Gas, or Propane Gas, with the proper burner.
Boiler
Kit
Duct Dia.
Wall
Opening
3 sections
FDVS 4
4”
6½”
4 to 9 sections
FDVS 6
6”
8½”
IMPORTANT
Standard indoor PF Series boilers are furnished
as knockdown boilers and are shipped as four
components (w/o FDVS) or five components
(with FDVS) are shown below:
• basic boiler assembly
• boiler jacket
• accessory kit
• burner (without post purge)
• FDVS parts (include post purge oil burner
for oil-fired burners)
Weatherproof (outdoor) PF Series boilers are
furnished as knockdown boilers only and are
shipped as five components as shown below:
• basic boiler assembly
• weatherproof boiler jacket
• exhaust cap, pipe, and weather collar
• accessory kit
• burner
On knockdown oil burners, the oil burner nozzle
is not included. Correctly sized nozzle must be
installed prior to startup.
Indoor oil-fired models PFO (3, 4, 5, 3T, 4T, 5T)
without direct exhaust system are available as
packaged boilers, in which case an oil burner
nozzle for one of three specified firing rates will
be factory installed in the oil burner.
Summary of Contents for ULTIMATE PF Series
Page 2: ......
Page 16: ...16 BURNER WIRING RIELLO BURNER WIRING...
Page 17: ...17 MULTI ZONE SYSTEM WIRING AND PIPING...
Page 18: ...18 MULTI ZONE SYSTEM WIRING AND PIPING...
Page 19: ...19 PIPING WITH CIRCULATORS MULTI ZONE SYSTEM WIRING AND PIPING...
Page 20: ...20 MULTI ZONE SYSTEM WIRING AND PIPING...
Page 38: ...38 BOILER PARTS...
Page 44: ......