APPENDIX A - CONTROL MODULE

A.5 Operation

Module continuously monitors boiler water temperature and 

fires or shuts off burner based on this temperature data.

1. 

When “Call for Heat” occurs, control enables circulator 

and monitors boiler water temperature to determine 

whether thermostat can be satisfied without firing 

burners.  

Table 6  - Operation State Codes

State 

Code 

Number

Definition

Explanation

1

Idle

or

Circulator

Standby - no call for heat

Heat request present. Boiler temperature sufficiently high to run circulator pump 

only.

4

Pre-purge

System is purging before ignition trial; includes Pilot Valve circuit diagnostics.

6

Spark

System sparking.  Flame is not present.

7

Flame stabilization

Flame signal is being established.  Variation in signal is allowed during this state, 

flame must be stable at end of period

8

Running

System is running.  Flame signal must be present.

9

Post-Purge

System is purging at end of call for heat

10

Retry Recycle Delay

Successful ignition was not detected, and delay is called before retry.
Flame signal was lost during state 7 or 8, and delay is called before retry (32 

second delay)

13

Soft lock-out

Soft lockout duration is one hour, may override with manual reset.

14

Hard lock-out

Manual reset is required for hard lockout

15

Wait for limit to close

Possible thermostat call for heat; limit switch is open.

16

Flame out of sequence

Flame signal sensed before trial for ignition.  Appropriate alarm is sent. 
OR
Flame signal sensed out of sequence during post purge.  Appropriate alarm is 

sent.                       OR
Flame signal present when not expected.  Appropriate alarm is sent.

17

Pilot valve diagnostics

Pilot valve circuitry diagnostics during pre-purge.

Current leakage detection Self check performed at start up, again at beginning of heat cycle, and during 

“Wait for Recovery “ State.

Wait for recovery

Self check performed at start up, again at beginning of heat cycle, and during 

“Wait for Recovery “ State

18

Wait for damper to open

Control has signaled damper/pressure switch 

to close, and is waiting for completion.                                                                                                     

If damper/pressure switch does not close within 60 seconds, control goes to 

State 20.

19

Wait for damper to close

Damper is closed and control waits for damper to open. 

Checked  at  beginning  of  heat  cycle  before  opening  damper.                                                                   

If damper does not open in 60 seconds, control goes to State 21.

20

Wait  for  damper  to  open            

(Failed close)

Damper has not opened (end switch not closed) at beginning of heat cycle.   

Alarm message is sent, control is NOT in lockout.

21

Wait  for  damper  to  close              

(Failed open)

Damper has not closed despite actuator de-energized.                                 

Alarm message is sent, control is NOT in lockout.

2. 

Control determines burner operation is required, 

module proceeds to start burner (see state codes list) 

and heats water in boiler until setpoint temperature is 

achieved or thermostat is satisfied. . 

3. 

Burner is de-activated, ignition module completes 

heating cycle, returns to idle and waits for temperature 

to drop again. 

4. 

Circulator is turned on throughout “Call for Heat.”

Summary of Contents for PENNCO 15B III Series

Page 1: ...OPERATION MAINTENANCE MANUAL Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com Models 15B045FE 15B070FE 15B096FE 15B120FE 15B145FE 15B170FE 15B19...

Page 2: ...17 11 Wiring Diagram 18 12 Lighting Instructions 20 13 Normal Sequence Of Operation 21 14 General Instructions 21 15 Checking Gas Input Rate To Boiler 23 Appendix A Control Module 24 A 1 Installation...

Page 3: ...R FUTURE REFERENCE WARNING Keep boiler area clear and free from combustible materials gasoline and other flammable vapors and liquids DO NOT obstruct air openings to the boiler room Modification subst...

Page 4: ...a level United States over 2000 ft 610m above sea level Reduce input rate 4 for every 1 000 ft 304m above sea level 2 Net AHRI Water Ratings shown based on piping and pickup allowance of 1 15 Consult...

Page 5: ...15B070 15 7 5 28 2015 16 415 16 1 15B096 15 7 5 28 2015 16 415 16 1 15B120 19 9 6 29 217 16 57 16 1 15B145 19 9 6 29 217 16 57 16 1 15B170 22 113 16 7 30 2115 16 515 16 1 15B195 22 113 16 7 30 2115 1...

Page 6: ...ance operation and service circulator replacement condensate trap control replacement etc 6 Locate boiler on level solid base as near chimney as possible and centrally located with respect to heat dis...

Page 7: ...if known air infiltration rate is less than 0 40 air changes per hour See Table 3 for space with boiler only Use equation for multiple appliances Volume 50 ft3 x Total Input Mbh Known Air Infiltratio...

Page 8: ...equal to or greater than that of the relief valve outlet over the entire length of discharge line have no intervening shutoff valve between safety relief valve and discharge to atmosphere do not plug...

Page 9: ...iler and safety relief valve Systems with automatic fill valves require back flow prevention device Install discharge piping from safety relief valve See Warning Page 8 When boiler is connected to hea...

Page 10: ...D COOLING ELEMENT CIRCULATOR A PRESSURE REDUCING VALVE PROPER BACKFLOW PROTECTION DEVICE GATE VALVE PURGE VALVE NOTICE Circulators in following illustrations are mounted on system supply side mounting...

Page 11: ...ss Piping Options Page 9 5 CONNECTING SUPPLY AND RETURN PIPING Figure 3 Bypass Piping Automatic Mixing Valve See Bypass Piping Options Page 9 BOILER WATER INLET ALTERNATE CIRCULATOR LOCATION TO SYSTEM...

Page 12: ...12 5 CONNECTING SUPPLY AND RETURN PIPING Figure 5 Single Zone System With DHW Priority Figure 6 Multi Zone System with Circulators and DHW Priority...

Page 13: ...13 5 CONNECTING SUPPLY AND RETURN PIPING Figure 7 Multi zone System With Zone Valves And DHW Priority With Circulator Figure 8 Multi zone System With Zone Valves And DHW Priority With Zone Valve...

Page 14: ...sizing any portion of the common venting system the common venting system should be re sized to approach the minimum size determined using the appropriate tables in Chapter 13 of the National Fuel Ga...

Page 15: ...ndicator must be in visible location following installation 5 Thermostat s heat anticipator must be adjusted to match total current draw of all controls associated with boiler during heating cycle 8 V...

Page 16: ...le 3 Support piping with hooks straps bands brackets hangers or building structure components to prevent or dampen excessive vibrations and prevent strain on gas connection Boiler will not support pip...

Page 17: ...ion 3 Circulator connection 4 Line power connections 5 LWCO kit 550002998 includes wiring instructions and wiring diagrams If using a different LWCO refer to the specific instructions provided with th...

Page 18: ...AGRAM I Figure 12 Integrated High Limit Electronic Ignition Control WARNING Modification substitution or elimination of factory equipped supplied or specified components may result in personal injury...

Page 19: ...19 11 WIRING DIAGRAM Figure 13 Integrated High Limit Electronic Ignition Control...

Page 20: ...ctions To Turn Off Gas To Appliance and call qualified service technician or your gas supplier TO TURN OFF GAS TO THE APPLIANCE 1 Set the thermostat to lowest setting 2 Turn off all electric power to...

Page 21: ...aks are found have them repaired immediately Check and maintain circulators Refer to circulator manufacturer s instructions Inspect venting system at the start of each heating season Check vent pipe f...

Page 22: ...d pilot for signs of corrosion rust or scale buildup Area around boiler must be kept clear and free of combustible materials gasoline and other flammable vapors and liquids Free flow of combustion and...

Page 23: ...us 0 3 inches water column from specified pressure Primary air adjustment is not necessary therefore air shutters are not furnished as standard equipment Air shutters can be furnished on request where...

Page 24: ...well and is not loose Refer to enclosed addendum for wiring instructions when using indirect hot water heater Verify vent damper connection is made See page 15 A 3 Adjusting Settings To discourage una...

Page 25: ...ial for ignition Appropriate alarm is sent OR Flame signal sensed out of sequence during post purge Appropriate alarm is sent OR Flame signal present when not expected Appropriate alarm is sent 17 Pil...

Page 26: ...for retry or reset at thermostat Check for correct installation and wiring before replacing any component Control module cannot be repaired If it malfunctions it must be replaced Use only qualified s...

Page 27: ...larm reason disappears 63 Soft lockout maximum number of recycles exceeded After main burner ignition Soft lockout 64 Soft Lockout electronics failure On board self diagnostics detected error Soft loc...

Page 28: ...amaged wire Check for cracked ceramic insulator which can cause short to ground and replace igniter sensor if necessary At gas valve disconnect main valve wire from MV terminal Turn on power and set t...

Page 29: ...29 NOTES...

Page 30: ...30 NOTES...

Page 31: ...31 Company Address Phone Company Name Tech Initials Service Performed Date SERVICE RECORD...

Page 32: ...erride which is provided primarily to permit the use of an external energy management system that serves the same function THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITION...

Reviews: