Installation and service instructions

for contractors

VIESMANN

Vitogate 300
Type BN/MB

BMS communication with heating systems via BACnet and Modbus

VITOGATE 300

5837535 GB

9/2018

Please keep safe.

Summary of Contents for Vitogate 300

Page 1: ...Installation and service instructions for contractors VIESMANN Vitogate 300 Type BN MB BMS communication with heating systems via BACnet and Modbus VITOGATE 300 5837535 GB 9 2018 Please keep safe ...

Page 2: ...system Working on the system Isolate the system from the power supply e g by removing the separate fuse or by means of a mains isolator and check that it is no longer live Safeguard the system against reconnection Danger Hot surfaces can cause burns Before maintenance and service work switch OFF the appliance and let it cool down Never touch hot surfaces on the boiler burner flue system or pipewor...

Page 3: ...difications to the building characteristics are not permissible e g cable pipework routing cladding or partitions Danger Leaking or blocked flue systems or an inade quate supply of combustion air can cause life threatening poisoning from carbon monoxide in the flue gas Ensure the flue system is in good working order Vents for supplying combustion air must be non closable Extractors Operating appli...

Page 4: ...ol unit into LON 14 LON system number and subscriber number 14 Updating LON subscriber list 15 Carrying out subscriber check 15 Commissioning the Vitogate 15 Making the connection to the Ethernet network 15 Enabling the DHCP server 15 Making the connection to the Vitogate 300 configuration webserver 16 Calling up the Vitogate 300 configuration webserver 16 Functions of the reset button 16 Restarti...

Page 5: ...o place or Acoustic signal Fit new component or In conjunction with a tool Clean the sur face Dispose of component correctly Dispose of component at a suitable collec tion point Do not dispose of component in domestic waste Intended use The Vitogate product is intended to be installed and operated only in conjunction with Vitotronic control units with due attention paid to the associated installa ...

Page 6: ...ms shall be deemed inappropriate Incorrect usage or operation of the appliance e g the appliance being opened by the system user is prohibi ted and will result in an exclusion of liability Incorrect usage also occurs if the components in the Viessmann system are modified from their intended function Product information The Vitogate 300 gateway type BN MB is designed for hooking up Vitotronic contr...

Page 7: ...se the following functions in conjunction with a BACnet or Modbus control system Transferring heating system operating states Setting heating system parameters Relaying of fault and error messages Preparing for installation Preparing for installation 5837535 Installation ...

Page 8: ...e may impair data transfer and cause damage to the device Maintain ambient temperatures of 25 to 70 C Increased line losses occur at 55 C or above Connecting cables Length Standard delivery Connecting cable from Vitogate to power supply unit 0 4 m Network cable can be extended on site by IT expert 2 m Accessories LON cable 7 m The LON connection can be extended with accessories see LON communica t...

Page 9: ...onnectors screened F USB connection for software updates Setting the DIP switch In the delivered condition the DIP switches are set to OFF The functions are disabled If interface RS485 is used set DIP switches 1 and 2 to ON If the Vitogate 300 is at the beginning or end of the RS485 network set DIP switch 3 to ON Power supply unit OUTPUT DC 24V 0 75A INPUT AC 100 240V N L Fig 2 INPUT 230 V 50 Hz O...

Page 10: ...changeable Note When connecting on site components including a PC laptop observe the insulation requirements of IEC EN 60335 Connection with LON cable C A A B D C D Fig 3 Installation spacing 7 m A Vitotronic control unit B Vitogate 300 C Terminator D LON cable 7 m long Connection with LON cable and LON coupling C E A A B E D D D E E D D C D Fig 4 Installation spacing 7 to 21 m A Vitotronic contro...

Page 11: ...upply and implement all safety measures e g RCD circuit in accordance with IEC 364 the connection requirements of your local power supply utility and VDE or national regulations Protect the power cable to the Vitogate 300 power supply unit with a fuse with a maximum rating of 16 A Isolators for non earthed conductors Install an isolator in the power cable to provide omnipolar separation from the m...

Page 12: ...itotronic control unit has appropriate fuse protection 3 Terminate the power cable on site in terminal box E and at plug fÖ Danger Incorrect core assignment can result in seri ous injury and damage to the appliance Take care not to interchange wires L1 and N L1 Brown BN N Blue BU PE Green yellow GNYE 4 Insert plug fÖ into the Vitotronic control unit Power supply independent of the mains isolator W...

Page 13: ...300 and OUTPUT on the power supply unit using the connecting cable supplied 0 4 m long 2 Check whether the power cable to the Vitotronic control unit has appropriate fuse protection 3 Terminate the power cable on site in terminal box D and at plug fÖ Danger Incorrect core allocation can result in serious injury and damage to the appliance Take care not to interchange wires L1 and N L1 Brown BN N B...

Page 14: ... network e g framing errors Illuminates red Indication prior to a reset whilst files are being connected Integrating the Vitotronic control unit into LON The LON communication module accessory must be plugged into the Vitotronic control unit LON system number and subscriber number Note Data transfer via LON can take several minutes Set LON system number LON subscriber number and further functions ...

Page 15: ...on 7 or 10 Crossed network cable Making the connection to the Ethernet network Connect the computer network card to the RJ45 LAN connection of the Vitogate 300 by means of a crossed network cable Note If a configuration file is to be loaded via a PC for sev eral gateways within a network a pause of at least ten minutes must be observed between the applications Alternatively the ARP cache of the PC...

Page 16: ...start The status LED then lights up in the same colour as before the restart Temporarily activating the static IP address on the Vitogate 300 If for example the current IP address of the Vito gate 300 is unknown yet you still want to access the Vitogate 300 without restoring its factory settings The Vitogate 300 is temporarily assigned the static IP address 169 254 0 1 Press and hold the reset but...

Page 17: ...e Vitogate 300 for at least 15 s While the reset button is pressed the status LED flashes orange red and green simultaneously The status LED remains off until the reset process is com plete Commissioning and adjustment Functions of the reset button cont 5837535 Service ...

Page 18: ...18 Commissioning and adjustment Functions of the reset button cont 5837535 Service ...

Page 19: ...19 The following details are required when ordering parts Serial no see type plate A Position number of the part from this parts list Parts lists Ordering parts 5837535 Components ...

Page 20: ...20 0005 0006 0002 0001 0003 Fig 10 Parts lists Vitogate 300 5837535 Components ...

Page 21: ...e BN MB 0002 Network cable length 2 m 0003 Power supply unit 24 V 0 75 A 0005 Connecting cable power supply 24 V and RS485 connector 0006 Vitogate 300 type BN MB installation and service instructions Parts lists Vitogate 300 cont 5837535 Components ...

Page 22: ...ondensing Dimensions height x width x depth 100 x 48 x 70 mm Installation Mounting rail TS 35 to EN 50022 Power supply unit Rated voltage 100 to 240 V Rated frequency 50 to 60 Hz Rated current 0 8 to 0 4 A Output voltage 24 V 1 Max output current 0 75 A Protection class II IP rating IP 20 Primary secondary earth separation SELV to EN 60950 Electrical safety EN 60335 Permissible ambient temperature...

Page 23: ...stem are not part of ordi nary household waste For decommissioning the system isolate the system from the power supply and allow components to cool down where appropriate All components must be disposed of correctly Appendix Final decommissioning and disposal 5837535 Appendix ...

Page 24: ...tives and supplementary national requirements in terms of its design and operational characteristics Conformity has been verified with the CE designation Using the serial number the full Declaration of Con formity can be found on the following website www viessmann co uk eu conformity Certificates Declaration of conformity 5837535 Service ...

Page 25: ... communication module 14 LON communication module installing 8 M Modbus 6 9 O Output current 22 Output voltage 22 Overview of connections Power supply unit 9 Vitogate 300 9 P Power supply Guidelines 11 Independent of mains isolator 12 Regulations 11 Via mains isolator 11 Power supply unit Ambient temperature 22 IP rating 22 Output current 22 Output voltage 22 Protection class 22 Rated current 22 R...

Page 26: ...26 5837535 ...

Page 27: ...27 5837535 ...

Page 28: ... Shropshire TF1 7YP GB Telephone 44 1952 675000 Fax 44 1952 675040 E mail info uk viessmann com Viessmann Werke GmbH Co KG D 35107 Allendorf Telephone 49 6452 70 0 Fax 49 6452 70 2780 www viessmann com 5837535 Subject to technical modifications ...