58
9 - START UP PROCEDURE
**
See Tables : Section 12.4 -Parameters for High Altitude
9.16 Description Of Parameters: Factory Settings conti.
FACTORY SETTINGS
75
100,
125,165
115,
150,205
P73
Boiler Power Selection
1
= 115
2
= 75/100
3
= 150
10
= 125
11
= 205
12
= 165
Default depends on firing rate of
boiler as listed.
P74
CH mode burner ignition delay after burner off due to water temperature exceeding limit setting with an interrupted call for
heat
Range
=
0-255 seconds (0-4.25 min.)
0
P78
0-10V Input
0
= Disabled
1
= Temperature Setpoint (3V = minimum setpoint, 10V = maximum setpoint
2
= Power Setpoint (3V = minimum power, 10V = maximum power)
0
P82
4
= Disabled
3
= Enabled 0-10V DC Input
4
NOTE
: To scroll to parameter
42
and above
it is necessary to set
P22
to
22
before scrolling up to the parameter.
The values listed below are factory defaults, there may be differences for each application
Model
75
100
115
125
150
165
205
Fuel
Natural
LP
Natural
LP
Natural
LP
Natural
LP
Natural
LP
Natural
LP
Natural
LP
P70
Ignition
Fan
Speed**
Setting
35
35
35
35
35
35
38
38
38
38
44
44
44
44
RPM
3500
3500
3500
3500
3500
3500
3800
3800
3800
3800
4400
4400
4400
4400
P71*
Maximum
Fan
Speed**
Setting
85
85
85
85
220
220
115
65
220
170
105
120
225
220
RPM
5850
5850
5850
5850
7200
7200
6150
5650
7200
6700
5550
5700
7250
7200
P72
Minimum
Fan
Speed**
Setting
50
50
50
50
55
55
40
25
40
35
43
45
40
45
RPM
1250
1250
1250
1250
1300
1300
1150
1000
1150
1100
1180
1200
1150
1200
To calculate fan
speeds
(P70 x 100)
(P71 x 10) + 5000
* For 165 Model: (P71 x 10) + 4500
(P72 x 10) + 750
240013501 REV A [03/15/2022]
Summary of Contents for Dunkirk DCB-100
Page 2: ...DCC 205...
Page 4: ...DCB 165...
Page 79: ...75 A 2 MODEL 75 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013501 REV A 03 15 2022...
Page 80: ...76 APPENDIX A WIRING DIAGRAMS A 2 MODEL 125 Heat Only 240013501 REV A 03 15 2022...
Page 81: ...77 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013501 REV A 03 15 2022...
Page 82: ...78 APPENDIX A WIRING DIAGRAMS A 1 MODEL 115 Combi 240013501 REV A 03 15 2022...
Page 83: ...79 APPENDIX A WIRING DIAGRAMS A 4 MODEL 150 Combi 240013501 REV A 03 15 2022...
Page 84: ...80 APPENDIX A WIRING DIAGRAMS A 5 MODEL 205 Combi 240013501 REV A 03 15 2022...
Page 85: ...81 NOTES 240013501 REV A 03 15 2022...
Page 86: ...82 NOTES 240013501 REV A 03 15 2022...
Page 121: ...33 PN 240011430 REV Q 03 15 2022 75 100 HEAT ONLY WIRING DIAGRAM MODEL 75 100 HEAT ONLY...
Page 122: ...34 PN 240011430 REV Q 03 15 2022 MODEL 125 HEAT ONLY 125 HEAT ONLY WIRING DIAGRAM...
Page 123: ...35 PN 240011430 REV Q 03 15 2022 MODEL 165 HEAT ONLY 165 HEAT ONLY WIRING DIAGRAM...
Page 124: ...36 PN 240011430 REV Q 03 15 2022 115 COMBI WIRING DIAGRAM MODEL 115 COMBI...
Page 125: ...37 PN 240011430 REV Q 03 15 2022 MODEL 150 COMBI 150 COMBI WIRING DIAGRAM...
Page 126: ...38 PN 240011430 REV Q 03 15 2022 MODEL 205 COMBI 205 COMBI WIRING DIAGRAM...
Page 132: ...44 PN 240011430 REV Q 03 15 2022 LOW WATER CUTOFF DETAIL LOW WATER CUTOFF NO NO YES...
Page 137: ...49 PN 240011430 REV Q 03 15 2022 3 FAULT SOLUTION SECTIONS...