28141 Rev A 10-27-06
21
TABLE A-12: AIRFLOW CHARACTERISTICS – DIRECT DRIVE
CFM
External Static Pressure – Inches w.c.
Furnace Model
Motor
HP
Blower
∆
T
Motor
FLA
Speed
0.20 0.25 0.30 0.40 0.50 0.60
High 1810 1775 1740 1675 1585 1510
Med-High 1570 1555 1540 1495 1445 1375
Med-Low 1090 1085 1080 1070 1065 1050
BCL(S)
BFL
80 – 145
1/2 HP
G10
85°F
7.0
Low 710 700 700 690 665 650
High 2188 2161 2133 2069 2016 1933
Medium 1742 1730 1718 1702 1670 1604
BCL(S)
BFL
80 – 145 (T)
1 HP
DCT1220-1104-5
85°F
12.3
14.0 MAX
Low 1410 1410 1410 1390 1374 1326
TABLE A-13: AIRFLOW CHARACTERISTICS – BELT DRIVE
CFM
External Static Pressure – Inches w.c.
Furnace Model
Motor
HP
Motor
FLA
∆
T
Blower
Blower
Pulley
Motor
Pulley
Turns
Out
0.20 0.25 0.30 0.40 0.50 0.60
0 1425
1355
1280
1125
905
516
2 1280
1200
1125
915
555
256
4 1115
1020
905
530
225 11
BCL(S)
80 – 120
BFL
80 – 120
1/3 HP
5.4
85°F
G10
7 x ¾
6
920
800
645
190
- - -
- - -
0
1535 1475 1410 1250 1065 845
2 1440
1370
1295
1090
880
472
4 1320
1250
1170
970
625
319
BCL(S)
80 – 145
BFL
80 – 145
1/2 HP
7.8
85°F
G10
6 x ¾
6 1225
1140
1040
835
435
132
Continued on next page.
Summary of Contents for BCL
Page 23: ...28141 Rev A 10 27 06 23 TABLE B 1 BECKETT AND RIELLO CHIMNEY VENTED WIRING DIAGRAM BCL S BFL ...
Page 24: ...28141 Rev A 10 27 06 24 TABLE B 2 BECKETT AND RIELLO DIRECT VENT WIRING DIAGRAM BCL S BFL ...
Page 29: ...29809 Rev A 10 19 2006 29 ...
Page 32: ...29809 Rev A 10 19 2006 32 ...
Page 36: ...29809 Rev A 10 19 2006 36 ...
Page 41: ...28141 Rev A 10 27 06 NOTES ...
Page 42: ...28141 Rev A 10 27 06 ...
Page 43: ...28141 Rev A 10 27 06 ...