37
Cool Fluid when air temperature exceeds [PAR51 (in °C)
+PAR53 (in 0.1°C)].
In Stove mode with water pump:
The stop temperature
based on the air temperature measurement is the same as
above. The water stop temperature is defined with PAR95.
In Boiler/Burner mode:
this parameter defines the stop level
in xx°C.
Flue gases temperature settings
No.
Parameter
Description
54
Ignition Test Gases
Temperature
Ignition Test gases temperature (in °C):
Defines the temperature threshold in the Ignition Test
sequence when the controller starts checking the flue gases
temperature slope. If the temperature rises for at least 3
°C/min and the flue gases temperature exceeds PAR56, the
device enters the Burning phase after 45 seconds.
55
Modulation Start Gases
Temperature
Gases modulation start temperature (in °C):
Flue gases temperature threshold, when the controller begins
to decrease the burning power.
IMPORTANT:
When setting this parameter the actual value is
double the value, entered in PC-PRO or UI, except for stoves,
where value in PC-PRO is the actual value, and value in UI is
doubled.
Example:
Stoves Other configurations
Value in PC-PRO
360
180
Value in UI
180
180
Actual parameter value
360°C
360°C
56
Heating Device OFF Gases
Temperature
Stop Fire exit temperature (in °C):
In the Stop Fire sequence the FAN1 operates until the flue
gases temperature falls below PAR56.
57
Maximum (Error) Gases
Temperature
Alarm triggering gases temperature (in °C):
If the flue gases temperature exceeds PAR57, the Alarm Gases
is reported and the controller switches off the system.
IMPORTANT:
When setting this parameter the actual value is
double the value, entered in PC-PRO or UI, except for stoves,
where value in PC-PRO is the actual value, and value in UI is
doubled.
Example:
Stoves Other configurations
Value in PC-PRO
400
200