30
7
Ignition Test Feeder 1
OFF Time
Ignition Test sequence feeder OFF time:
Defines the feeder pause during the Ignition Test sequence.
8
Ignition Test Feeder 1
ON Time
Ignition Test sequence feeder ON time:
Defines the feeder dosing time during the Ignition Test sequence.
Feeder: Burning
9
Power 1 Feeder 1 OFF
Time
Power 1 feeder OFF time:
Defines the feeder pause at power level 1 in the Burning phase.
10
Power 1 Feeder 1 ON
Time
Power 1 feeder ON time:
Normal regulation
- defines the feeder dosing time at power level 1.
Advanced regulation
- defines the MINIMUM dosing time for the PID
regulator. Controller calculates the feeder dosing time for each
power PID regulator output. Maximum number of steps is 1024.
11
Power 2 Feeder 1 OFF
Time
Power 2 feeder OFF time:
Defines the feeder pause at power level 2 in the Burning phase.
NOTE: Not used when advanced regulation is selected.
12
Power 2 Feeder 1 ON
Time
Power 2 feeder ON time:
Defines the feeder dosing time at power level 2 in the Burning phase.
NOTE: Not used when advanced regulation is selected.
13
Power 3 Feeder 1 OFF
Time
Power 3 feeder OFF time:
Defines the feeder pause at power level 3 in the Burning phase.
NOTE: Not used when advanced regulation is selected.
14
Power 3 Feeder 1 ON
Time
Power 3 feeder ON time:
Defines the feeder dosing time at power level 3 in the Burning phase.
NOTE: Not used when advanced regulation is selected.
15
Power 4 Feeder 1 OFF
Time
Power 4 feeder OFF time:
Defines the feeder pause at power level 4 in the Burning phase.
NOTE: Not used when advanced regulation is selected.
16
Power 4 Feeder 1 ON
Time
Power 4 feeder ON time:
Defines the feeder dosing time at power level 4 in the Burning phase.
NOTE: Not used when advanced regulation is selected.
17
Power 5 Feeder 1 OFF
Time
Power 5 feeder OFF time:
Defines the feeder pause at power level 5 in the Burning phase.
NOTE: Not used when advanced regulation is selected.
18
Power 5 Feeder 1 ON
Time
Power 5 feeder ON time:
Normal regulation
- defines the feeder dosing time at power level 5.
Advanced regulation
- defines the MAXIMUM dosing time for the
PID regulator. Controller calculates the feeder dosing time for each
power PID regulator output. Maximum number of steps is 1024.
Fan settings
No.
Parameter
Description