24
2.2 System Parameter:
Code
Parameter Name
Set Range
Factory Setting
1
Return Difference for
Target Water Temp.
1~18
℃
(2~36
℉
)
1
℃
(2
℉
)
2
Set Temp. in Cooling Mode
8
℃
~35
℃
(46~95
℉
)
27
℃
(81
℉
)
3
Set Temp. in Heating Mode
5
℃
~40
℃
(41~104
℉
)
27
℃
(81
℉
)
4
Compensation Value of Inlet Water Temp. -5
℃
~15
℃
(-9~30
℉
)
0
℃
(0
℉
)
5
Defrosting Cycle
20MIN~90MIN
45MIN
6
Defrosting Start Temp.
-9
℃
~-1
℃
(16~30
℉
)
-3
℃
(27
℉
)
7
Defrosting Time
5MIN~20MIN
8MIN
8
Temp.to Exit Defrosting
1
℃
~40
℃
(33~104
℉
)
15
℃
(59
℉
)
9
Difference between
Ambient Temp. and Coil Temp.
to Start Defrosting
0
℃
~15
℃
(0~30
℉
)
5
℃
(10
℉
)
10
Ambient Temp.to Start
Defrosting
0
℃
~20
℃
(32~68
℉
)
17
℃
(63
℉
)
11
Working Cycle of EEV
20S~90S
25S
12
Degree of Superheat in Smart/
Powerful Mode
-5
℃
~10
℃
(-9~20
℉
)
Depends on
Actual Model
13
Exhaust Temp. for Modifying
EEV
70
℃
~125
℃
(158~257
℉
)
95
℃
(203
℉
)
14
Opening of EEV during Defrosting
( Set Value*10=Actual Steps)
2~45
Depends on
Actual Model
15
Min. Steps of EEV
(Set Value*10=Actual Steps)
5~15
10
16
Working Mode of EEV
0 Manual/1 Auto
1
17
Manual Steps of EEV
(Set Value*10=Actual Steps)
2~45
35
Summary of Contents for NE-F50SP/R4INV-PA
Page 2: ......
Page 14: ...11 Model NE F110SP R4INV PA NE F150SP R4INV PA NE F180SP R4INV PA...
Page 15: ...12 Model NE F210SP R4TINV PA NE F250SP R4TINV PA NE F280SP R4TINV PA...
Page 16: ...13 3 Explosion View...