26
F7
Frequency set_7
20~120Hz
F8
Frequency set_8
20~120Hz
F9
Frequency set_9
20~120Hz
10
Frequency set_10
20~120Hz
11
Frequency set_11
20~120Hz
12
Frequency set_12
20~120Hz
13
Frequency set_13
20~120Hz
14
Frequency set_14
20~120Hz
15
Frequency set_15
20~120Hz
16
Frequency set_16
20~120Hz
17
Frequency set_17
20~120Hz
18
Frequency set_18
20~120Hz
19
DC fan speed_1
0~99 (*10)
According to the actual model
20
DC fan speed_2
0~99 (*10)
According to the actual model
21
DC fan speed_3
0~99 (*10)
According to the actual model
22
DC fan speed_4
0~99 (*10)
According to the actual model
23
DC fan speed_5
0~99 (*10)
According to the actual model
24
DC fan speed_6
0~99 (*10)
According to the actual model
25
Silent mode superheat
-5~10
℃
According to the actual model
26
Model selection
0:Heating & Cooling
1:Heating ONLY
2:Cooling ONLY
0
27
Constant temp. superheat
-5~10
℃
According to the actual model
B
Exhaust temp. set_F11
50~125
℃
95
℃
(203
℉
) According to the actual model
C
Exhaust temp. set_F12
50~125
℃
100
℃
(212
℉
) According to the actual model
D
Exhaust temp. set_F13
50~125
℃
105
℃
(221
℉
) According to the actual model
E
Exhaust temp. set_F14
50~125
℃
110
℃
(230
℉
) According to the actual model
F
Exhaust temp. set_F15
80~125
℃
115
℃
(239
℉
) According to the actual model
In the above table, when the serial number reaches F10, the serial number only shows the number,
that is, 10. For example, 1080 is displayed as F10 in the query of parameter.
2.3 Trouble shooting
system protection/ error indication
Error code
Error description
Solutions
Er 03
Water flow protection
Check water flow /switch, change the switch if
necessary
Er 04
Winter anti-freezing
Water pump will run automatically for first grade
antifreeze
Summary of Contents for NE-F50SP/R4INV-PA
Page 2: ......
Page 14: ...11 Model NE F110SP R4INV PA NE F150SP R4INV PA NE F180SP R4INV PA...
Page 15: ...12 Model NE F210SP R4TINV PA NE F250SP R4TINV PA NE F280SP R4TINV PA...
Page 16: ...13 3 Explosion View...
Page 52: ...49 2 1...
Page 53: ......
Page 54: ......