background image

MODES & STAGING

TIME DELAY

 

TIME DELAY IS DESIGNED FOR EQUIPMENT PROTECTION.  AFTER CALLS FROM ALL ZONES HAVE BEEN SATISFIED AND THE EQUIPMENT IS DE-

ENERGIZED, A 3-MINUTE TIME DELAY WILL BE COMPLETED BEFORE NEW THERMOSTAT CALLS WILL BE PROCESSED.  DURING THE DELAY ALL 

DAMPERS OPEN AND THE EQUIPMENT WILL NOT RUN.  DURING DELAY THE DIGITAL DISPLAY WILL COUNT DOWN THE NUMBER OF SECONDS 

LEFT DURING PURGE TIME IF A NEW CALL IS ENERGIZED. NOTE: 

ALTHOUGH SMARTZONE WILL NOT ENERGIZE THE FAN (OR EQUIPMENT) 

DURING DELAY, THE EQUIPMENT BEING USED MAY HAVE A BUILT IN CONTROL THAT CAUSES THE FAN TO CONTINUE RUNNING.

A 3 MINUTE PURGE OF THE SUPPLY AIR PLENUM IS INITIATED DURING OPPOSING-CALL CHANGEOVER. (SWITCHING FROM HEAT TO COOL 

OR COOL TO HEAT) DURING THE PURGE, THE FAN WILL REMAIN ENERGIZED TO PURGE EXISTING SUPPLY AIR TEMPERATURE AND TO 

ALLOW  EQUALIZATION  OF  HVAC  SYSTEM  PRESSURES  BEFORE  ENERGIZING  THE  OPPOSING  MODE  CALL.  DURING  THE  PURGE  MODE, 

ZONE(S) CALLING FOR THE OPPOSITE MODE WILL HAVE DAMPER(S) CLOSED. ALL OTHER DAMPERS (NON-CALLING ZONE(S) AND ZONE(S) 

CALLING  FOR  MODE  LAST  ENERGIZED)  WILL  REMAIN  OPEN  DURING  PURGE  MODE.  THE  DIGITAL  DISPLAY  WILL  SHOW  180  SECOND 

COUNTDOWN TIMER DURING PURGE PROCESS (SEE “AUTO CHANGEOVER” ABOVE)

AUTO CHANGEOVER

IT  IS  POSSIBLE  TO  SIMULTANEOUSLY  HAVE  ONE  ZONE(S)  CALLING  FOR  COOL  AND  ANOTHER  ZONE(S)  CALLING  FOR  HEAT  (CALLED 

“OPPOSING CALLS”). WHEN OPPOSING CALLS EXIST, EACH ACTIVE MODE RUNNING ON THE EQUIPMENT WILL BE LIMITED TO A MAXIMUM 

RUN  TIME  OF  15  MINUTES  STARTING  WHEN  THE  OPPOSING  MODE  CALL  IS  RECEIVED.  IF  THE  ACTIVE  MODE  DOES  NOT  SATISFY  THE 

CALLING ZONE(S) IN THIS 15 MINUTE INTERVAL, SMARTZONE WILL INITIATE A CHANGEOVER PROCESS. CHANGEOVER: DE-ENERGIZE THE 

ACTIVE  MODE  AND  INITIATING  A  3  MINUTE  PURGE  (SEE  BELOW  FOR  MORE  ABOUT  PURGE).  AFTER  PURGE,  OPPOSING  MODE  WILL 

ENERGIZE IF CALL FROM ZONE FOR THIS MODE STILL REMAINS ACTIVE.

EMERGENCY HEAT CAN ONLY BE OPERATED BY A HEAT PUMP THERMOSTAT CONNECTED TO THE ZONE 1 THERMOSTAT ‘W’ TERMINAL.  

IF ZONE 1 THERMOSTAT CALLS FOR EMER. HEAT, THE SMARTZONE SYSTEM WILL BE LOCKED INTO EMERGENCY HEAT. 

 THE COMPRESSOR WILL NOT ENERGIZE AND ONLY HEATING CALLS WILL BE RECOGNIZED FROM ANY ZONE OTHER THAN ZONE 1. 

ONLY W1/EH AND G WILL BE ALLOWED TO ENERGIZE WHILE SMARTZONE IS LOCKED INTO EMERGENCY HEAT.  (I.E. COMPRESSOR & 

COOLING CALLS WILL BE LOCKED OUT)  ALL COOLING CALLS FROM ZONES 2 & UP WILL BE IGNORED AND ANY HEATING CALL FROM 

ZONES 2 & UP WILL BE TREATED BY THE SMARTZONE SYSTEM AS EMER. HEAT TO THE EQUIPMENT (INCLUDING ‘W’ OR ‘Y’)

TO UNLOCK EMER. HEAT TAKE THE SMARTZONE SYSTEM BACK TO NORMAL OPERATION, REMOVE THE EMER. HEAT CALL FROM THE 

ZONE 1 THERMOSTAT AND MAKE A CALL FOR COMPRESSOR HEAT OR COOLING FROM ZONE 1 THERMOSTAT.

EMERGENCY HEAT

DUAL FUEL (

FOSSIL

 

FUEL

 

AUX

 / 

EM

 

HEAT

)

IN DUAL FUEL MODE, THE COMPRESSOR(S)  WILL NOT RUN WHEN AUXILIARY HEAT IS ENERGIZED.   SMARTZONE CONTROLS DUAL FUEL 

OPERATION SO A “DUAL FUEL KIT” AND HEAT PUMP THERMOSTATS ARE NOT REQUIRED.  GAS/ELECTRIC THERMOSTATS MAY BE USED WITH 

A HEAT PUMP SYSTEM, HOWEVER, A HEAT PUMP STAT IS NECESSARY FOR ZONE 1 TO CONTROL EMERGENCY HEAT (DESCRIBED ABOVE).  

ALWAYS INSTALL THE HEAT PUMP EVAPORATOR DOWNSTREAM OF THE FURNACE, THIS PREVENTS CONDENSATION IN THE HEAT EXCHANGER 

DURING THE COOLING MODE.  SEE EQUIPMENT STAGING TO THE RIGHT FOR MORE DETAILS ABOUT DUAL FUEL.

PURGE

1

THE SMARTZONE CONTROLS EQUIPMENT STAGING AUTOMATICALLY BASED ON TIME AND SUPPLY AIR TEMPERATURE.  (THIS TEMPERATURE 

IS READ BY THE INCLUDED SUPPLY AIR TEMP SENSOR – SAS)  NOTE:

 WITHOUT THIS SENSOR INSTALLED, THE SMARTZONE WILL NOT RUN 

2

ND

 STAGE OR OPERATE ANY DAMPERS.  

TIME AND TEMPERATURE SETTINGS VARY ACCORDING TO THE TYPE OF EQUIPMENT HI/LO TEMP 

LIMIT SETTINGS.  STAGING WILL OCCUR ONLY WHEN THE MINIMUM RUN-TIME AND TEMPERATURE RANGE CONDITIONS ARE MET.  THE 

FACTORY DEFAULT SETTINGS FOR TEMPERATURE CUT-IN AND CUT-OUT ARE ADJUSTABLE. (SEE “HI & LO LIMIT ADJUST” PAGE 9)

OPERATION

11

HEAT PUMP ONLY:

I80

HI TEMP

LO TEMP

SUPPLY

PURGE

DELAY ECO

I80

HI TEMP

LO TEMP

SUPPLY

PURGE

DELAY

ECO

SECONDS

COUNTDOWN

SECONDS

COUNTDOWN

REVERSING VALVE

IN ORDER TO REDUCE UNNECESSARY OPERATION THE REVERSING VALVE WILL REMAIN IN THE SAME STATE THAT WAS LAST 

CALLED FOR BY A ZONE THERMOSTAT EVEN AFTER THE CALL HAS BEEN SATISFIED AND EQUIPMENT STOPPED RUNNING.

Summary of Contents for SmartZone ZS2X-2.0

Page 1: ...ONE 4X ZS4X 2 0 8E HI TEMP LO TEMP SUPPLY PURGE DELAY ECO THERMOSTATS HEAT PUMP OR GAS ELECTRIC EASY TO READ DISPLAY LEDs SHOW HEAT COOL CALLS NO VOLTMETER REQUIRED SCREWLESS WIRING TERMINALS FRESH AI...

Page 2: ...STAGE HEAT OR REVERSING VALVE ORANGE 10 AMP 24VAC CONTACT RATING 40VA POWER CLOSE SPRING OPEN DAMPERS 10VA POWER OPEN SPRING CLOSE DAMPERS 10VA POWER OPEN POWER CLOSE DAMPERS 3VA LABEL DESCRIPTION LE...

Page 3: ...DED BY ANY ADDITIONAL PRESSURE RELIEF q REFER TO DUCT DESIGN BYPASS PAGE 3 4 q CALCULATE MINIMUM 24VAC TRANSFORMER VA CAPACITY PAGE 5 q CHECK PRIMARY AND SECONDARY VOLTAGE FOR ZONING TRANSFORMER MAKE...

Page 4: ...E CFM CFM ROUND CFM CHART BYPASS PRESSURE RELIEF BYPASS SIZING SELECT A DAMPER SIZE WITH A MAX CFM GREATER THAN THE CFM NEEDED TO BYPASS USE THE FORMULA BELOW TO CALCULATE CFM NEEDED TO BYPASS AND THE...

Page 5: ...E SPEED EQUIPMENT AVOID CREATING MORE THAN THREE ZONES WITH NO ZONE SMALLER THAN 20 OF THE TOTAL EQUIPMENT CFM CAPACITY RETURN AIR UNDERSIZED RETURN AIR DUCTS REGISTERS CAN RESULT IN PROBLEMS DUE TO I...

Page 6: ...DETAILS IN ZONING GUIDE ENERGIZES FAN AFTER 90 SECOND DELAY WITH HEATING 2ND STAGE ACTIVE NORMAL AUX HEAT COMPRESSOR ELECTRIC HEAT STRIPS REVERSE VALVE ON IN COOLING EQUIPMENT GAS ELECTRIC STANDARD HE...

Page 7: ...TRIC OR DUAL FUEL AFTER COIL BEFORE BLOWER SAS INCLUDED ALWAYS TO THE LEFT EXCEPT FOR 5 THROUGH 20 ZONES DETAILS PAGE 14 ENERGIZES FAN IMMEDIATELY WITH HEATING 2ND STAGE ENERGIZES ONLY IF MORE THAN ON...

Page 8: ...ED NOTE ALWAYS DISCONNECT POWER TO SMARTZONE WHILE MAKING ANY WIRING CHANGES DO NOT USE EQUIPMENT TRANSFORMER 24 VAC COMMON TRANSFORMER PRIMARY INSTALLATION DO NOT CONNECT POWER UNTIL ALL WIRING IS CO...

Page 9: ...G 24VAC R HEATING EH O B PC PO COM POWER OPEN POWER CLOSE 24 VAC 2 3 VA SPRING OPEN POWER CLOSE 24 VAC 6 10 VA DAMPERS SUPPLY TEMP EQUIPMENT REQUIRES SEPARATE TRANSFORMERS FOR HEAT AND COOL NOTE RELAY...

Page 10: ...2 STAGE GAS ELECTRIC H2 2 STAGE HEAT PUMP 4 HI TEMP LO TEMP SUPPLY PURGE DELAY ECO ZONE PRESS RELEASE THE UP ARROW BUTTON WHEN THE DISPLAY IS SHOWING SUPPLY TEMPERATURE THE HI TEMP INDICATOR WILL FLA...

Page 11: ...LS OTHER ZONES WILL ONLY OPEN AND CLOSE DAMPERS AS NEEDED FLASH ON SE SETTING CHANGES STORED IN MEMORY THIS WILL SHOW UP AFTER ADJUSTING ANY SETTING INCLUDING STAT TYPE LIMIT TEMPERATURES AND FRESH AI...

Page 12: ...E SMARTZONE SYSTEM WILL BE LOCKED INTO EMERGENCY HEAT THE COMPRESSOR WILL NOT ENERGIZE AND ONLY HEATING CALLS WILL BE RECOGNIZED FROM ANY ZONE OTHER THAN ZONE 1 ONLY W1 EH AND G WILL BE ALLOWED TO ENE...

Page 13: ...10 2ND STAGE WILL NOT RE ENERGIZE UNTIL AFTER 3 MINUTES OFF TIME IF SUPPLY TEMP IS WARMER THAN HI TEMP SEE ADJUST LIMITS FAN WILL RUN BUT W1 WILL DE ENERGIZE FOR 3 MINUTES AND UNTIL SUPPLY TEMP IS CO...

Page 14: ...LAY ECO 2 3 PRESS TO SELECT THE OF MINUTES PER HOUR FOR FRESH AIR RUN TIME IN 5 MINUTE INCREMENTS PRESS STAT TYPE BUTTON TO SELECT ZONE 4 PRESS UP BUTTON TO SELECT FA PRESS STAT TYPE AGAIN 4 0 HI TEMP...

Page 15: ...HE PRIMARY AND SECONDARY POLARITY MUST BE THE SAME ON ALL SMARTZONE 4X BOARDS 24VAC 24VAC FIRMWARE VERSION SHOWN ON DISPLAY AFTER RESET OR POWER UP CONNECT EQUIPMENT SAS ONLY TO MAIN ZONES 1 4 SMARTZO...

Page 16: ...FAN SPEED WIRING POWER ETC ANY PROBLEM ASSOCIATED WITH THE EQUIPMENT A INCOMPATIBLE POWER STEALING NO COMMON B DEFECTIVE THERMOSTAT C WIRING DEFECT D STAT TYPE SETUP HEAT PUMP ONLY A ACTUATOR FAILURE...

Reviews: