SET THERMOSTAT TYPE
ADJUST HI AND LO LIMIT
DISPLAY
I88
HI TEMP
LO TEMP
SUPPLY
PURGE
DELAY
ECO
MULTI-FUNCTION DIGITS SHOW SUPPLY TEMPERATURE, CUT-OUT TEMPERATURES
(HIGH AND LOW), ZONE THERMOSTAT TYPES, FRESH-AIR TIME.
DELAY
SMARTZONE CONTROLLER HAS SATISFIED ALL
CALLS AND WILL DELAY 3 MIN BEFORE INITIATING
ANY ADDITIONAL CALLS, COUNTDOWN TIMER ON
DIGITS SEC. IF CALL MADE.
I80
PURGE
SYSTEM IS IN PURGE MODE FOR EQUIPMENT
CHANGEOVER (FAN [G] AND DAMPERS CONTINUE TO
OPERATE, COUNTDOWN TIMER ON DIGITS SEC.)
I80
SETTING HIGH TEMP LIMIT – PRESS UP OR DOWN
ARROW BUTTONS TO ADJUST THE HIGH TEMP LIMIT
(FACTORY DEFAULT: HEAT PUMP – 120
O
F; ELECTRIC
HEAT – 135
O
F; GAS HEAT – 135
O
F)
HI TEMP
HIGH TEMP LIMIT SENSED, SMARTZONE CONTROLLER
DE-ENERGIZES EQUIPMENT HEAT OUTPUT FOR A
MINIMUM OF 3 MINUTES (FAN [G] AND DAMPER
OUTPUTS CONTINUES TO OPERATE)
(FLASH)
(ON)
LO TEMP
LOW TEMP LIMIT SENSED, SMARTZONE
CONTROLLER DE-ENERGIZES EQUIPMENT COOL
OUTPUT FOR A MINIMUM OF 3 MINUTES (FAN [G]
AND DAMPER OUTPUTS CONTINUE TO OPERATE)
SETTING LOW TEMP LIMIT – PRESS THE UP OR
DOWN ARROW BUTTONS TO ADJUST THE LOW
TEMP LIMIT (FACTORY DEFAULT 48
O
F)
(FLASH)
(ON)
SUPPLY
SUPPLY AIR TEMPERATURE
DISPLAYED NORMALLY
= SAS DISCONNECTED
IF ZONE 4 HAS BEEN CONFIGURED FOR FRESH AIR AND
FRESH AIR IS BEING CURRENTLY SATISFIED. FAN
SHOULD BE RUNNING AND ZONE 4 (FA DAMPER)
ENERGIZED IN THE OPEN POSITION
ECO
EC INPUT ON ZONE 1 IS ENERGIZED AND SYSTEM IS IN
ECONOMY MODE. ONLY ZONE 1 CAN INITIATE
EQUIPMENT CALLS, OTHER ZONES WILL ONLY OPEN AND
CLOSE DAMPERS AS NEEDED.
(FLASH)
(ON)
SE
= SETTING CHANGES STORED IN MEMORY,
THIS WILL SHOW UP AFTER ADJUSTING
ANY SETTING INCLUDING STAT TYPE, LIMIT
TEMPERATURES, AND FRESH AIR TIME.
OPERATION
PRESS & HOLD THE
▼
”DOWN” ARROW BUTTON FOR 5 SECONDS WHEN THE DISPLAY IS SHOWING SUPPLY
TEMPERATURE. WHEN RELEASED THE “HI LIMIT” AND “ECO” INDICATORS WILL FLASH AND THE DIGITS WILL
SHOW THE CURRENTLY SET TEMPERATURE (DEFAULT = 60, ADJUSTABLE FROM 58 TO 68 USING
▲▼
BUTTONS)
ADJUST
SETTINGS
STAT
TYPE
G2
PURGE
CO
WARNING:
USING THIS
FEATURE REDUCES
THE EFFECTIVENESS
OF SMARTZONE'S
ENERGY SAVING
STAGING CONTROLS
AND MAY INCREASE
ENERGY USAGE.
WITH ZONE 1 “STAT TYPE” SET TO G2 OR H2, DIP # 4
·
OFF (DEFAULT) – SMARTZONE’S ONBOARD STAGING CONTROL [TIME&TEMP]
WILL CONTINUE TO OPERATE 2
ND
STAGE. ZONE 1 STAT WILL BE ABLE TO
ENERGIZE 2
ND
STAGE EARLY BUT WILL NOT PREVENT 2
ND
STAGE FROM
OCCURRING.
·
ON (LOCKOUT) – SMARTZONE’S ONBOARD STAGING CONTROL DISABLED AND
ZONE 1 THERMOSTAT WILL BE ABLE TO CONTROL STAGING. (THIS INCLUDES
AUXILIARY HEAT FOR HEAT PUMP)
ZONE 1 STAGING CONTROL ALLOWS A MULTI-STAGE THERMOSTAT CONNECTED
TO ZONE 1 TO CONTROL UP TO 2 COOL AND 3 HEAT STAGES. G2 (GAS/ELECTRIC)
OR H2 (HEAT PUMP) THERMOSTAT TYPE CAN BE SELECTED IN HEAT PUMP MODE.
NOTE: SMARTZONE WILL DELAY 60 SECONDS BETWEEN 1
ST
STAGE START AND 2
ND
STAGE
START. ALSO, A 3 MINUTE MINIMUM OFF TIME IS IMPLEMENTED FOR ALL EQUIPMENT
CALLS. STAGING FROM ZONE 1 THERMOSTAT WILL NOT OVER-RIDE THESE TIME DELAYS.
NOTE 2: WHEN ZONE 1 STAT TYPE IS SET TO G2 OR H2, “ECO MODE” IS DISABLED. TO
ENABLE ECO MODE, SET ZONE 1 STAT TYPE TO GE OR HP.
ZONE 1 STAGING
G2
HI TEMP
LO TEMP
SUPPLY
PURGE
DELAY ECO
Z
O
N
E
1
S
T
A
T
R
EC
Y
G
O/B
W
C
C
R
Y1
W2
G
W1
Y2
GAS/ELECTRIC
MULTI-STAGE
THERMOSTAT
R
EC
Y
G
O/B
W
C
Z
O
N
E
1
S
T
A
T
C
R
Y1
Y2
G
(Aux/EH)
O/B
HEAT PUMP
MULTI-STAGE
THERMOSTAT
H2
HI TEMP
LO TEMP
SUPPLY
PURGE
DELAY ECO
10
--