2
2
SET THERMOSTAT TYPE
1
1
CONFIGURATION
ADJUST HI AND LO LIMIT
FOR PROTECTION, THE EQUIPMENT WILL NOT RUN ABOVE HI OR BELOW LO LIMITS. SEE EQUIPMENT STAGING FOR DETAILS.
ON HEAT PUMP EQUIPMENT ONLY, EITHER GAS/ELECTRIC OR HEAT PUMP THERMOSTATS CAN BE USED. THE SMARTZONE CONTROLLER
MUST BE SET FOR THE THERMOSTAT TYPE BEING USED OR THE EQUIPMENT WILL NOT OPERATE PROPERLY WITH POTENTIAL RISK OF
DAMAGE. SET THE THERMOSTAT TYPE AS SHOWN BELOW USING THE “STAT TYPE” AND “ARROW” BUTTONS. NOTE:
WHEN CONFIGURED
FOR GAS/ELECTRIC EQUIPMENT (SEE DIP SWITCHES), ONLY GAS/ELECTRIC THERMOSTATS CAN BE USED.
NOTE 2:
WHEN USING
SMARTLINK FOR 5+ ZONE SYSTEM, SECONDARY CONTROLLER STAT TYPE MUST ALSO BE SET USING THE SAME METHOD.
SET HIGH TEMP LIMIT (CUT-OUT)
SET LOW TEMP LIMIT (CUT-OUT)
NOTE: CHANGING EITHER THE LOW OR HIGH TEMP LIMIT WILL ALSO AFFECT THE STAGING CUT-IN AND CUT-OUT TEMPERATURES
SETTINGS. ADJUSTING THESE CAN CAUSE STAGING TO OCCUR SOONER OR LATER . SEE EQUIPMENT STAGING FOR MORE DETAILS.
SET AUX. HEAT LIMIT (CUT-IN)
SET ECONOMIZER MODE LIMIT (CUT-OUT)
PRESS THE STAT
TYPE BUTTON...
PRESS THE UP AND
DOWN ARROWS
IF FA IS SELECTED, ZONE 4
DAMPER WILL OPERATE AS A
FRESH AIR DAMPER.
SEE FRESH AIR FOR DETAILS
ZONE:
I
HI TEMP
LO TEMP
SUPPLY
PURGE
DELAY ECO
H2 AND G2 ONLY ON ZONE 1 ALLOW
THERMOSTAT TO CONTROL STAGING.
SEE ZONE 1 STAGING FOR DETAILS
HOLD
HOLD
9
GE
= GAS / ELECTRIC
HP
= HEAT PUMP
G2
= 2 STAGE GAS/ELECTRIC
H2
= 2 STAGE HEAT PUMP
4
HI TEMP
LO TEMP
SUPPLY
PURGE
DELAY ECO
ZONE:
PRESS & RELEASE THE
▲
”UP” ARROW BUTTON WHEN THE DISPLAY IS SHOWING SUPPLY TEMPERATURE.
THE “HI TEMP” INDICATOR WILL FLASH AND THE DIGITS WILL SHOW THE CURRENTLY SET TEMPERATURE. THIS HIGH LIMIT CUT-OUT CAN BE
ADJUSTED UP OR DOWN USING THE
▲▼
BUTTONS. SEE EQUIPMENT STAGING BELOW FOR MORE DETAILS.
PRESS & RELEASE THE
▼
”DOWN” ARROW BUTTON WHEN THE DISPLAY IS SHOWING SUPPLY TEMPERATURE.
THE “LO TEMP” INDICATOR WILL FLASH AND THE DIGITS WILL SHOW THE CURRENTLY SET TEMPERATURE. THIS LOW LIMIT
CUT-OUT CAN BE ADJUSTED UP OR DOWN USING THE
▲▼
BUTTONS. SEE EQUIPMENT STAGING BELOW FOR MORE DETAILS.
I35
HI TEMP
LO TEMP
SUPPLY
PURGE
DELAY ECO
48
HI TEMP
LO TEMP
SUPPLY
PURGE
DELAY ECO
90
HI TEMP
LO TEMP
SUPPLY
PURGE
DELAY
ECO
PRESS & HOLD THE
▲
”UP” ARROW BUTTON FOR 5 SECONDS WHEN THE DISPLAY IS SHOWING SUPPLY
TEMPERATURE. WHEN RELEASED THE “HI LIMIT” AND “DELAY” INDICATORS WILL FLASH AND THE DIGITS WILL
SHOW THE CURRENTLY SET TEMPERATURE (DEFAULT = 90, ADJUSTABLE FROM 90 TO 94 USING
▲▼
BUTTONS)
OR
GE
FA
= FRESH AIR
GE
HP
OR
PRESS & HOLD THE
▼
”DOWN” ARROW BUTTON FOR 5 SECONDS WHEN THE DISPLAY IS SHOWING SUPPLY
TEMPERATURE. WHEN RELEASED THE “HI LIMIT” AND “ECO” INDICATORS WILL FLASH AND THE DIGITS WILL
SHOW THE CURRENTLY SET TEMPERATURE (DEFAULT = 60, ADJUSTABLE FROM 58 TO 68 USING
▲▼
BUTTONS)
ZONES:
2
HI TEMP
LO TEMP
SUPPLY
PURGE
DELAY ECO
3
HI TEMP
LO TEMP
SUPPLY
PURGE
DELAY ECO
GE
HP
60
HI TEMP
LO TEMP
SUPPLY
PURGE
DELAY
ECO
G2
CO
OR
RE
CO
MM
EN
DE
D
STRONGLY RECOMMENDED TO LEAVE AT DEFAULT SETTINGS UNLESS APPLICATION DEMANDS ADJUSTMENT.