49
disassembling or moving the stove or pipe
without tools.
Aluminium belt and silicone of
high temperature (300°C).
RECOMMENDABLE
If the pipe is not equipped with sealing rings
Ventillation grills.
OBLIGATORY
Insert stoves. See drawing 7.
Thermally insulated extensible
pipe.
OBLIGATORY
Ducting of convection air (Ductable stoves).
Air distribution group.
RECOMMENDABLE
In case of excessive load loss / pipe lengt
(Ductable stoves).
Ø60 pipe. resistant to constant
temperatures of 120 °C
OBLIGATORY
Teide model. Connection for lateral convectors.
AIRTIGHT INSTALLATION. "DIFLUX" mounting and
direct connection to the outside. Air intake pipe
connection.
“DIFLUX” piping
OBLIGATORY
AIRTIGHT INSTALLATION. "DIFLUX" mounting.
LOCATION AND SAFETY DISTANCES.
4.11.
Do not install the stove in a sleeping room.
4.12.
Install a fire protection between the ground and the stove if the floor is a combustible material.
4.13.
Security distances should be respected when the stove is installed in spaces where materials around it, be it
the construction material itself, the fuel or any other type of materials, are likely to be flammable. Ensuring a
better access to the stove for future maintenance or repair work is also worth considering.
Drawing 6
INSTALLATION OF BUILT-IN STOVES
The measurement of the lateral ventilation openings indicates the effective area of air passage through
them. If a decorative grid is placed, the effective area of air passage of the said grid must coincide with the effective
area of passage of the openings, varying the dimensions (height and / or width) of the grids to achieve the right air
passage area.
Drawing 7 shows the minimum permitted dimensions of the built-in space (non-flammable material) with
respect to the stove and the position of the ventilation grids, for the installation of the
Córdoba
,
Córdoba
ducted
,
Teide
and
Granada
models.
A
Lateral wall.
≥ E
B
Back
of
the
stove.
Minimum
separation that allows visualizing the
label marking the stove.
≥ 80 mm
C
1.5 x depth of stove.
See dimensions
D
Shelf.
≥ 600 mm
E
Depth of stove.
See dimensions
Effective
grid
area
left
side.
OBLIGATORY.
≥ 200x120mm
Effective grid area right.
OBLIGATORY.
≥ 200x120mm
Isolated output gas pipe within the
socket.
OBLIGATORY.
Ø80mm
Thermally insulated convection air
ducting.
OBLIGATORY
.
Ø100mm