background image

pag.21

LB972  

MULTICALOR 300.1-400.1 PR/AB     

B

The  ionization  current  is  checked  by  inserting  a

microammeter with an end of scale of 1000 µA (d.c.) in

series with the UV CELL. A faulty position of the elec-

trode  can  lead  to  a  reduction  in  the  ionization  current

and  cause  a  safety  cut-out  of  the  burner  due  to  a  flame

detection  failure.  In  this  case,  check  the  position  of  the

electrode, its electric connection and the earthing of the

burner. The ionization current is normally > 70 µA.

IONIZATION CURRENT

22 23

LANDIS

 

LFL 1.622

Fotocellula

min 70 

µ

A

Microamperometro 

fondo scala 1000 

µ

A

REMOVING THE BLAST TUBE

REMOVING THE FIRING HEAD

ADJUSTMENT OF GAS MINIMUM PRESSURE SWITCH

Unscrew off and remove cover M. - Set regulator N to a value equal to 60% of  gas nominal

feed pressure (i.e. for nat. gas nom. pressure = 20 mbar, set regulator to a value of 12 mbar;

for L.P.G. nom. pressure of G30/G31- 30/37 mbar, set regulator to a value of 18

mbar).Screw up cover M

ADJUSTMENT OF THE AIR PRESSURE SWITCH

Unscrew screws A and B and remove cover C.- Set the pressure switch to the mini-

mum by turning regulator D to position 1. 

- Start the burner and keep in low flame running, while checking that combustion is

correct. Through a small cardboard, progressively obstruct the air intake until to

obtain a CO2 increase of 0,5÷0,8% or else, if a pressure gauge is available, connected

to pressure port E, until reaching a pressure drop of 1 mbar (10 mm of W.G.). -

Slowly increase the adjustment value of the air pressure switch until to have the bur-

ner lockout. Remove the obstruction from the air intake, screw on the cover C and

start the burner by pressing the control box rearm button.

Note: The pressure measured at pressure port E must be within the limits of the pressu-

re switch working range. If not, loose the locking nut of screw F and gradually turn the same:

clockwise to reduce the pressure; counterclockwise to increase. At the end tighten the locking nut.

2,5

5

10

15

50

25

3

5

3

0

40

45

20

0,4

0,6

0,9

3

,0

1,

5

2,1

1,

8

2,4

2,7

1,2

I

L

M

N

A

B

C

D

E

F

G

H

gas pressure 

switch

air pressure switch

Summary of Contents for Multicalor 300.1 PR

Page 1: ...LB1448 20 07 2005 Multicalor 300 1 PR MD Multicalor 400 1 PR MD Light oil Natural gas 40 300 mbar Light oil LPG 75 300 mbar MODELS A BRUCIATORI MISTI GAS GASOLIO B GAS LIGHT OIL DUAL BURNERS...

Page 2: ...atural Gas L C V 8 570 kcal Nm3 LPG L C V 22 260 kcal Nm3 Light oil L C V 10 200 kcal kg max visc 1 5 E at 20 C OVERALL DIMENSIONS Burner output Backpressure in combustion chamber I M L E D D1 F C B A...

Page 3: ...the air servocontrol in approximately 30 seconds time When the servocontrol is fully open a signal to the electronic control unit starts the 66 seconds pre purge cycle At the end of the prepurging tim...

Page 4: ...ation probe which cuts in and sets the burner shutdown within the safety time In case of gas lack or a major pressure drop the minimum air pressure switch shuts down the burner Ref Description t1 Dura...

Page 5: ...STING THE MAXIMUM CAPACITY OF THE GAS Position the selector situated on the control panel on position 1 and proceed as follows Adjusting the maximum gas flow rate see figure on solenoid valve adjustme...

Page 6: ...p cover M ADJUSTMENT OF THE AIR PRESSURE SWITCH Unscrew screws A and B and remove cover C Set the pressure switch to the mini mum by turning regulator D to position 1 Start the burner and keep in low...

Page 7: ...st be suitable for burner The connection of boiler s thermostats and all the safeties The motor rotation direction The correct calibration of the motor s thermal protection When all the above mentione...

Page 8: ...button on the control box If after a successful pump priming the burner locks out after the prepurging due to a fuel pressure drop in the pump rearm the burner s lock out to restart the burner Do neve...

Page 9: ...p 5 Selector 0 Loking of devoices for operating at intermediate outputs Operation at max output Operation at min output AUTO Automatic operation 6 Main switch I O 7 Selector 0 Light oil Gas 8 Lockout...

Page 10: ...ses are blown out The control box is faulty THE BURNER RUNS THE PREPURGING AND SWITCHES TO LOCKOUT AT THE END OF CYCLE Check the fan and the air pressure Check the air pressure switch Control box faul...

Page 11: ...LOSE 1st Stage Increase power OPEN 2nd Stage Two stage operation Description of display and keys on the RWF 40 microprocessor regulator The figure shows the normal display indicating the actual value...

Page 12: ...to access the parameters level To move from one parameter to the next press PGM PGM When HYS1 is displayed burner ignition differential stage II increase or decrease the value using the and keys Conf...

Page 13: ...1 Connection for probe QAE2 passive probe Water probe Configuration code C111 9XXX Connection for probe FT TP passive probe Degusa probe Configuration code C111 5XXX Connection for probe QBE620 P act...

Page 14: ...faulty the regulator will not indicate the real value Situation The number 1999 blinks in the display as the actual value with SP E showing in the set point field Cause The external set point value i...

Page 15: ...e relative opening in the electrical panel A Insert the fixing anchors and screws into the slots and secure the unit to the panel B To open the regulator squeeze the cover from the ends as shown and l...

Page 16: ...ive probe QBE620 P QAE22 FT TP 1000 P4 P10 P16 P25 P40 Analog input 1 2 and 3 setpoint changeover shift C111 9030 5030 G000 G000 G000 G000 G000 Limit comparator controller type setpoint 1 locking C112...

Page 17: ...A UV 19 03 1998 Q N BEM43167 3 MULTICALOR 300 1 400 1 500 1 PR PR LANDIS SQM 50 481A2 LANDIS LFL 1 622 VPS 504 UV 11 03 2005 FMP 95 96 KMV R S T NO FMV MV U V W FMP MP U V W S R T KMP R S T NO SAMA 1...

Page 18: ...TV MV MP KA FU Z Q SWITCH OIL GAS COMMUTATORE GASOLIO GAS INTERRUPTEUR MAZOUT GAS CONMUTADOR GASOLEO GAS THERMOSTAT GRANDE PETIRE ALLURE HIGH LOW FLAME THERMOSTAT TERMOSTATO DI ALTA BASSA FIAMMA COMM...

Page 19: ...2005 FMP 95 96 KMP R S T NO KMV R S T NO MP U V W MV U V W Q HLB FMV FMP S R 10 11 8 5 6 7 9 T N FMV 95 96 SAgG 1 2 3 0 SAMA 1 2 3 0 FMV 97 98 HLBT GAS 2 GASOLIO 1 COMMUTATORE ALTA BASSA FIAMMA SWITC...

Page 20: ...LIO GAS INTERRUPTEUR MAZOUT GAS CONMUTADOR GASOLEO GAS TERMOSTATO DE SEGURIDAD COMMUTATORE MANUALE AUTOMATICO SWITCH MANUAL AUTOMATIC INTERRUPTEUR MANUEL AUTOMATIQUE CONMUTADOR MANUAL AUTOMATICO THERM...

Page 21: ...1 33 LFL 1 622 VPS 504 UV 22 06 2005 FMP 95 96 KMV R S T NO FMV MV U V W FMP MP U V W S R T KMP R S T NO SAMA 1 2 3 0 HLBT FMV 97 98 SAgG 1 2 3 0 GAS 2 GASOLIO 1 T P STC 50 Hz 400V HLB STAB T P STS R...

Page 22: ...MP KA FU Z Q SWITCH OIL GAS COMMUTATORE GASOLIO GAS INTERRUPTEUR MAZOUT GAS CONMUTADOR GASOLEO GAS THERMOSTAT GRANDE PETIRE ALLURE HIGH LOW FLAME THERMOSTAT TERMOSTATO DI ALTA BASSA FIAMMA COMMUTATOR...

Page 23: ...6 Q N BEM43188 1 MULTICALOR 300 1 400 1 500 1 PR PR LANDIS SQM 50 481A2 LANDIS LFL 1 333 LFL 1 622 PREDISPOSTO UV 03 11 2005 FMP 95 96 KMV R S T NO FMV MV U V W FMP MP U V W S R T KMP R S T NO SAMA 1...

Page 24: ...TATORE GASOLIO GAS INTERRUPTEUR MAZOUT GAS CONMUTADOR GASOLEO GAS THERMOSTAT GRANDE PETIRE ALLURE HIGH LOW FLAME THERMOSTAT TERMOSTATO DI ALTA BASSA FIAMMA COMMUTATORE MANUALE AUTOMATICO SWITCH MANUAL...

Page 25: ...400 1 PR AB Multicalor 300 1 PR MD Multicalor 400 1 PR MD 7 8 36 11 14 4 6 5 3 9 10 39 26 31 29 30 27 34 32 33 52 35 28 2 37 20 13 12 25 24 22 23 19 21 17 16 15 18 1 41 50 51 44 43 47 53 38 49 42 46 4...

Page 26: ...802 2 24 REL BASE Finder 5532 R905 R905 Finder 5534 R906 R906 25 REL Finder 5532 R711 R711 Finder 5534 R712 R712 26 UV CELL LANDIS QRA 2 A205 A205 27 IGNITION CABLE TC BFE01403 2 BFE01403 2 TL BFE0140...

Page 27: ...right to make without any prior notice all those modifications which it deems usefull and or necessary in order to improve the quality of its products without affecting their main features CEcoflam S...

Reviews: