29
www.ecoflam-burners.com
EN
420010463703
MAINTENANCE PROGRAM
ATTENTION:
to remove the nozzle use the
suitable box wrench taking care
to not damage the electrodes
.
Check the position of the
electrodes after any intervention
as wrong position could cause
ignition troubles.
Check and clean the gas filter
in the pilot gas valve
REMOVING
THE BLAST TUBE
REMOVING
THE FIRING HEAD
3 ÷ 4 mm
5 ÷ 6 mm
Ignition Electrode
POSITION OF ELECTRODES
22 2
3
S
IEMEN
S
min
70
ȝ
A
UV
C
E
LL
M
icroamperometer
f
u
ll
sca
l
e
1000
μ
A
L
F
L
1
.
333
The detector current is checked by inserting a
micro ammeter (scale 1000 μA - d.c.) in series
with the UV cell.
The flame detector current has to been > 70 μA.
GAS FILTER CLEANING - GAS PILOT FILTER CLEANING
ATTENTION:
Periodically clean oil cartridge
with gasoline and the gas filter cartridge with
air and replace them if it is necessary!
Summary of Contents for 3142132
Page 3: ...3 www ecoflam burners com EN 420010463703 CONFORMITY DECLARATION ...
Page 34: ...34 www ecoflam burners com EN 420010463703 APPENDIX Fluidics nozzle chart ...
Page 35: ...35 www ecoflam burners com EN 420010463703 APPENDIX Fluidics nozzle chart ...