E93.1001EN.C Manual CD
+
89
Now for every single water heater of the cascade the following two parameters must be selected and programmed
according to the above drawing.
Master:
C5
P5 DF
1
C2
P5 DA
0
Slave 1:
C5
P5 DF
0
C2
P5 DA
1
Slave 2:
C5
P5 DF
0
C2
P5 DA
2
And so on.
Menu C: Cascade
C 5
C a s
S i / M a
0
Function for the cascading of the water heater(s).
This parameter sets the function of the water heater at a
cascade alignment
0 = Slave unit
1 = Single / Master unit
Menu C: Cascade
C 2
B u s
a d d r e s s
0
Function for the cascading of the water heater(s).
This parameter determines the address of the water heater
for the total cascading control.
Master = 0, Slave1 = 1, etc.
When the correct parameter is set, this must be confirmed at the confirmation screen. After activation, the value
will blink for a few seconds while the parameter is programmed into the water heater.
is continued p.t.o.
→
P1
P1
P1
P1
P5DF = 1
P5DA = 0
P5DF = 0
P5DA = 1
P5DF = 0
P5DA = 2
P5DF = 0
P5DA = 3
17
A
18
B
CASCADE
CONNECTION
water
heater
master
water
heater
slave 1
water
heater
slave 2
water
heater
slave 3
PARAMETERS PARAMETERS PARAMETERS PARAMETERS