Menu structure UA 300 D
Controller type UR 141
83
E
2007 − ECKELMANN | BERLINER STRASSE 161 | 65205 WIESBADEN | FON +49(0)611 7103-0 | FAX 49(0)611 7103-133 | eckelmann.de
Version 2.03 27. Juni 2008
S
Screen 1−6 Not used with this controller type
S
Screen 1−7 Cooling Zone 2
COOLING 2
POS: XXXXX
Cooling
XXX
Current ON/OFF status of cooling Zone 2 Terminals 35/36/38
Run Time
XX %
Cooling relay on time during last day (00:00 − 24:00 hours)
Starts
X
Cooling relay actuations during last day
Temp. R4.3
XXX °C
Room air sensor R4.3 setpoint for comparison
Setpoint R4.3
XXX °C
Room air sensor R4.3 setpoint
Hystersis R4.3
XXX K
Room air sensor R4.3 hysteresis
S
Screen 1−8 Defrost Zone 2
DEFROST 2
POS: XXXXX
Counting Rate
X
Counting rate
Defrost Counter
X
Defrost counter
Defrost 2
XXX
Current ON/OFF status of defrosting Zone 2 Terminals 53/54
Temp. R1.3
XXX °C
Current temperature on evaporator sensor R1.3
Temp. R1.4
XXX °C
Current temperature on evaporator sensor R1.4
Def. End. Tmp.
XXX °C
Defrost termination temperature for comparison
Wait Time
XX m
Waiting time setpoint
Drip Time
XX m
Drip time setpoint
Last DefrstWe
XX hh:mm
Day and time of last defrost cycle started
S
Screen 1−9 Fans Zone 2
FANS 2
POS: XXXXX
Fans
XXX
Current ON/OFF status of fan Zone 2 Terminals 73/74
Temp. R1.3
XXX °C
Current temperature on evaporator sensor R1.3
Fan Delay
XX °C
Fan delay
Summary of Contents for UA 300 D
Page 2: ......
Page 6: ...Table of contents iv Version 2 03 27 Juni 2008 Notice ...
Page 8: ...System Design of UA 300 D 2 Version 2 03 27 Juni 2008 Notice ...
Page 40: ...Installation and Startup of UA 300 D 34 Version 2 03 27 Juni 2008 Notice ...
Page 54: ...Operation of UA 300 D 48 Version 2 03 27 Juni 2008 Notice ...
Page 100: ...Menu structure UA 300 D Controller type UR 141 94 Version 2 03 27 Juni 2008 Notice ...
Page 108: ...Specifications of UA 300 D 102 Version 2 03 27 Juni 2008 Notice ...