Pin and Terminal Assignments of UA 300 D
36
Version 2.03 27. Juni 2008
Relay outputs 230 V AC
Controller type
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
Relay 6
Relay 7
Terminal No.
15, 16, 18
25, 26, 28
35, 36, 38
43, 44
53, 54
63, 64
73, 74
Case controller
UA 111 X
UA 111 XP
Alarm
Alarm
Cooling 1
Cooling 1
Cooling 2
Cooling 2
Compressor 1
Compressor 1
Compressor 2
Compressor 2
−−−
Compressor 3
Fan
Fan
Coldroom controller
UR 141
Alarm
Cooling 1
Cooling 2
Defrost 1
Defrost 2
Fan 1
Fan 2
Digital outputs 24 V DC
Controller Type
Output 1
Output 2
Terminal No.
81, 82, 83
91, 92, 93
Case controller
UA 111 X
UA 111 XP
Case lighting
Not used
Not used
Not used
Coldroom controller
UR 141
Not used
Not used
Power supply
Controller Type
Power Supply
Protective Conductor
Terminal No.
N, L
All controllers
230 V AC
PE
Relay operation
The following table shows operating direction of the digital outputs for the separate controller types.
Controller type
Cooling
Defrost
Fan
Alarm
Compressor
UA 111 X
Positive
−−−
Inverted
Inverted
Positive
UA 111 XP
Positive
−−−
Inverted
Inverted
Positive
UR 141
Zone 1 (LT): Inverted
Zone 2 (NT): Positive
Positive
Positive
Inverted
−−−
Positive
means that operation of the relay is not inverted:
The relay is energized when the controller activates the function output (e.g. Cooling = ON).
(This means that the contact of a normally open relay is closed.)
The relay is not energized when the controller deactivates the function output (e.g. Cooling = OFF).
(This means that the contact of a normally open relay is open.)
Inverted
means that operation of the relay is inverted:
The relay is not energized when the controller activates the function output (e.g. Alarm = ON).
(This means that the contact of a normally open relay is open.)
The relay is energized when the controller deactivates the function output (e.g. Alarm = OFF).
(This means that the contact of a normally open relay is closed.)
Summary of Contents for UA 300 D
Page 2: ......
Page 6: ...Table of contents iv Version 2 03 27 Juni 2008 Notice ...
Page 8: ...System Design of UA 300 D 2 Version 2 03 27 Juni 2008 Notice ...
Page 40: ...Installation and Startup of UA 300 D 34 Version 2 03 27 Juni 2008 Notice ...
Page 54: ...Operation of UA 300 D 48 Version 2 03 27 Juni 2008 Notice ...
Page 100: ...Menu structure UA 300 D Controller type UR 141 94 Version 2 03 27 Juni 2008 Notice ...
Page 108: ...Specifications of UA 300 D 102 Version 2 03 27 Juni 2008 Notice ...