Function of UA 300 D
19
E
2007 − ECKELMANN | BERLINER STRASSE 161 | 65205 WIESBADEN | FON +49(0)611 7103-0 | FAX 49(0)611 7103-133 | eckelmann.de
Version 2.03 27. Juni 2008
S
NT coldrooms (normal−temperature coldrooms, UR 141 Zone 2 only)
The fan normally continues running during cooling and defrosting. When the parameter "
Overrun Time
" is set
greater than 0 and "
Fan Overrun
" is set other than −−", the fan starts simultaneously with cooling and stops with
a delay when cooling is stopped. Stop delay is contingent on two conditions, both of which must be fulfilled:
- The set overrun time must have expired.
- Temperature on the evaporator sensor must be at or above the "
Fan Overrun
" setpoint.
Verdampfer 2
Evaporator 2
Verdampfer 1
Evaporator 1
Valve 1
Return
air
R1.1
Return
air
Valve 2
R1.3
Supply
air
Supply
air
Fan 1
Fan 2
UA 300 D
ZNR.
51203
72
730
E0
Refrigeration point
controller
R1.1: Defrost
sensor
(Terminal
Z31/Z32)
R1.3: Defrost
sensor
(Terminal
Z81/Z82)
Valve 1:
Solenoid Valve 1 relay
(Terminal 25/26/28)
Valve 2:
Solenoid Valve 2 relay
(Terminal 35/36/38)
Fan 1:
Fan control relay
(Terminal 63/64)
Fan 2:
Fan control relay
(Terminal 73/74)
Summary of Contents for UA 300 D
Page 2: ......
Page 6: ...Table of contents iv Version 2 03 27 Juni 2008 Notice ...
Page 8: ...System Design of UA 300 D 2 Version 2 03 27 Juni 2008 Notice ...
Page 40: ...Installation and Startup of UA 300 D 34 Version 2 03 27 Juni 2008 Notice ...
Page 54: ...Operation of UA 300 D 48 Version 2 03 27 Juni 2008 Notice ...
Page 100: ...Menu structure UA 300 D Controller type UR 141 94 Version 2 03 27 Juni 2008 Notice ...
Page 108: ...Specifications of UA 300 D 102 Version 2 03 27 Juni 2008 Notice ...