Pin and Terminal Assignments of CI 3000 / SIOX
59
Version 2.09 09. April 2014
6.1.3
Terminal assignment for 230 V AC relay outputs
The two relay outputs PRIO1/PRIO2 can be used for sending alarm messages. The multifunctional output AUX
can be freely configured (see table). The terminals are located on the underside of the device.
Warning - hazardous electrical voltage!
Danger of electric shock! BEFORE and AFTER
connection it must checked
that the 230 V AC relay outputs are
off load
!
Low voltage
and
safety extra-low voltage must
not
be applied together
at the relay outputs 15/16/18, 25/26/28 and 35/36/38.
Falls die Alarmierung über ein Telefonwahlgerät mit den dafür vorgesehenen abfallverzögerten
Alarmkontakten PRIO1/PRIO2 erfolgt so sind diese einer zyklischen Kontrolle zu unterziehen um
sicherzustellen, dass die Kontakte auch bei Spannungsausfall noch melden.
In order to fuse the cable and relay outputs a circuit breaker with the following parameters is recom
mended for each relay output:
- Nominal current at 230 V AC: 6 A
- Tripping characteristic (type): B
Terminal No.
Function
15 (common)
16 (N.C.)
18 (N.O.)
Multifunctional output AUX: Can be configured (menu 6-1-4-1) as follows:
- Horn
- Modem hardware reset
- Additional alarm relay with the priority PrioX3, PrioX4, PrioX5,
PrioX6, PrioX7, PrioX8 or PrioX9
or
- For switching the modem to the DDC (T-connector required)
25 (common)
26 (closed by alarm)
28 (opened by alarm)
Alarm relay PRIO2: Alarm for messages with priority 2
35 (common)
36 (closed by alarm)
38 (opened by alarm)
Alarm relay PRIO1: Alarm for messages with priority 1
Light switch
(for switching of a protective circuit breaker)
1, 2
For switching of contactor with suppressor (
LIGHT
)
Summary of Contents for CI 3000
Page 20: ...Application of CI 3000 14 Version 2 09 09 April 2014 Notice...
Page 62: ...Installation and Startup of CI 3000 SIOX 56 Version 2 09 09 April 2014 Notice...
Page 118: ...Menu structure of CI 3000 112 Version 2 09 09 April 2014 Notice...
Page 120: ...Decommissioning and disposal 114 Version 2 09 09 April 2014 Notice...
Page 126: ...Alarms and Messages of CI 3000 120 Version 2 09 09 April 2014 Notice...