Installation and Startup of CI 3000 / SIOX
44
Version 2.09 09. April 2014
5.5.4
24 V DC supply via SIOX terminals 93 and 94
In addition to the maximum four SIOX Extension Modules the CI 3000 Store Computer can supply 24 V DC
power to other external loads. This power can be taken from terminals 93 (-) and 94 (+) on the SIOX Extension
Module.
Danger of failure of alarm messaging!
A short circuit on the terminals 91-95 (SIOX-SUPPLY)
leads to the failure of the CI 3000 store computer for the duration of the short circuit, and conse
quently the failure of the alarm messaging!
It is possible to power further external 24 V DC consumers (CAN bus repeater etc.) in addition to the
S0 interfaces however this is not recommended!
In the event that consumers are to be supplied via the terminals 93 (-) and 94 (+), then the maximum permissi
ble summation current must be calculated, taking in to consideration the following factors.
S
Max. total 24 V DC power supply of CI 3000 Store Computer:
24V DC / 600 mA
S
Current each SIOX Extension Modules for 8 relay outputs (24 V DC)
96 mA
Current each relay output
12 mA
S
Tolerance factor
80%
Max. total current [mA] = (600 mA - (No. of SIOX relay outputs * 12 mA)) * 0.8
If other loads to be supplied with power via terminals 93 (-) and 94 (+), the maximum allowable total current of
all SIOX Extension Modules must be determined with consideration to the following conditions:
No. of SIOX
Extension
Modules
No. of
relay
outputs
Current each SIOX
Tolerance factor 80%
Max. allowable
total current on all terminals 93 (-)
/ 94 (+)
1. SIOX
max. 8
8 * 12 mA = 96 mA
(600 mA - 96 mA) * 0,8
400 mA
2. SIOX
max. 16
16 * 12 mA = 192 mA
(600 mA - 192 mA) * 0,8
320 mA
3. SIOX
max. 24
24 * 12 mA = 288 mA
(600 mA - 288 mA) * 0,8
250 mA
4. SIOX
max. 32
32 * 12 mA = 384 mA
(600 mA - 384 mA) * 0,8
170 mA
Summary of Contents for CI 3000
Page 20: ...Application of CI 3000 14 Version 2 09 09 April 2014 Notice...
Page 62: ...Installation and Startup of CI 3000 SIOX 56 Version 2 09 09 April 2014 Notice...
Page 118: ...Menu structure of CI 3000 112 Version 2 09 09 April 2014 Notice...
Page 120: ...Decommissioning and disposal 114 Version 2 09 09 April 2014 Notice...
Page 126: ...Alarms and Messages of CI 3000 120 Version 2 09 09 April 2014 Notice...