Function of CI 3000
24
Version 2.09 09. April 2014
4.4
CAN bus station monitoring
The CI 3000 Store Computer performs cyclic check on presence of all LDS components previously detected in
the system. Failure of a component is detected by station monitoring and generates a
Computer Fault
alarm.
Every new LDS component connected to the CAN bus is detected via “plug and play” automatically by the store
computer and included in station monitoring (Screen 7-1).
The following CAN bus nodes can be present in the LDS system:
LDS components
CAN bus address
Max. no. of LDS components on CAN bus
Case controller of the UA 300 and UA 400 series
1..99
99
VS 3010 / VS 3010 BS / VS 3010 CT / VS 3010 WP
FS 3010 / VS 300 / VS 3010 C pack controllers
101..109
9
CI 3000 Store Computer
111
(fixed address)
1
AL 300 Operator Terminal
112 .. 116,
117 .. 120
Max. 9 or max. 5, if 4 receiver modules are
present in the system.
Receiver module WR 300
for wireless temperature sensors TS 30 W
117 .. 120
4 (only possible, if NO operator terminal
uses these CAN bus addresses)
LDSWin PC via COM port
121 (fixed address)
1
DDC modules of building control system (BCS)
122..125
Maximum of 4 if there are no Modbus TCP
master gateways installed in the system
LDSWin PC via CAN bus PC adapter
126 (fixed address)
1
LDSWin PC via LAN gateway
(from version 1.1c or higher)
126 or 127
1
Combi-Gateway
- LAN-Gateway
- XML-Gateway
- Modbus TCP-Master 1 Gateway
- Modbus TCP-Master 2 Gateway
- Modbus TCP-Master 3 Gateway
- Modbus TCP-Master 4 Gateway
126 oder 127
110
122
123
124
125
1
1
Maximum of 4 if there are no DDC modules
installed in the system.
In failure or shutdown of the CI 3000 Store Computer, the AL 300 Operator Terminal having the low
est CAN bus address (when used) performs monitoring for the duration of the outage.
4.5
Alarm suppression in manual shutdown of LDS components
Shutdown of an LDS component is detected by CAN station monitoring as a failure (Screen 7-1). This causes a
prompt to appear on the display of the CI 3000 Store Computer and all AL 300 Operator Terminals (when used)
asking whether the LDS component has been shut down intentionally.
The user can then confirm shutdown within 5 minutes by pressing ENTER. If confirmation is made within this
interval, monitoring of the LDS component concerned will be deactivated and accordingly it will
not
be reported
as failed.
Otherwise, or if the user answers no to the prompt by pressing the ESC key, the LDS component will as normal
be reported as failed. An LDS component that has been shut down is automatically re-included in station moni
toring when it is switched on again.
The manual shutdown of case controllers is entered in the store computer’s message list!
Summary of Contents for CI 3000
Page 20: ...Application of CI 3000 14 Version 2 09 09 April 2014 Notice...
Page 62: ...Installation and Startup of CI 3000 SIOX 56 Version 2 09 09 April 2014 Notice...
Page 118: ...Menu structure of CI 3000 112 Version 2 09 09 April 2014 Notice...
Page 120: ...Decommissioning and disposal 114 Version 2 09 09 April 2014 Notice...
Page 126: ...Alarms and Messages of CI 3000 120 Version 2 09 09 April 2014 Notice...