Alarms and Messages of CI 3000
117
Version 2.09 09. April 2014
No.
Messages
Cause
Correction
Monitoring
52 Controll.Fail. xxx
or
Controll.Fail. Mxx
No response by LDS-component to Store Com
puter requests.
Check power supply and LDS com
ponent connection to CAN bus, i.e.
Modbus.
53 Failure AHT xxx
No response by AHT component.
Possible causes:
- Controller failure
- AHT gateway failure
- Failure of link between AHT gateway and
CI 3000 Store computer
Check power supply and connec
tions on AHT components.
Communication
60
Call nnnnnnnn
Call to Store Computer from PC. nnnnnnnnnn
is number of LDSWin dongle. Remote PC
phone number is shown as station name.
-
Archive faults
81 Archive Fault
nn
Archive management error detected on restart.
Please contact Service Organization
82 Archive Error
nn
During operation an error occurred in the archi
ving (error number nn only for internal use)
1. All archives must be saved using
LDSWin (see chapter 6.10.1)
2. Following this, a reorganisation is
to be carried out using the key com
bination MODE + ESC + 6
In the event of uncertainty please
contact the Service Organization
83 Insuff. Memory
Archive could not be created for new compo
nent.
Please contact Service Organization
84 Insuff. Memory EU
EU archive could not be created for new com
ponent.
Please contact Service Organization
Summary of Contents for CI 3000
Page 20: ...Application of CI 3000 14 Version 2 09 09 April 2014 Notice...
Page 62: ...Installation and Startup of CI 3000 SIOX 56 Version 2 09 09 April 2014 Notice...
Page 118: ...Menu structure of CI 3000 112 Version 2 09 09 April 2014 Notice...
Page 120: ...Decommissioning and disposal 114 Version 2 09 09 April 2014 Notice...
Page 126: ...Alarms and Messages of CI 3000 120 Version 2 09 09 April 2014 Notice...