Echoflex Solutions Installation Guide

SmartSpace Controller–Gen 2

Connect 0–10V Dimming Output

WARNING:

RISK OF DEATH OR INJURY BY ELECTRIC SHOCK! 0–10V

wiring may not be fully isolated from high-voltage AC power. Do not
assume that 0–10V wiring is safe to touch, even when run as an NEC
Class 2 signal. Test for AC voltage to ground before terminating any 0–
10V control wiring to the device.

AVERTISSEMENT:

RISQUE DE MORT OU DE BLESSURE PAR

ÉLECTROCUTION! Le câblage 0–10V peut ne pas être complètement isolé
du courant alternatif haute tension. Ne supposez jamais que le câblage 0–
10V peut être touché en toute sécurité, même s'il est utilisé avec un
signal NEC de Classe 2. Testez la tension alternative par rapport à la
terre avant de raccorder tout câblage de commande 0–10V à l'appareil.

The 0–10V dimming output wiring exits the SmartSpace Controller–Gen 2
through the top nipple of the enclosure with the power wiring.

1.

Connect the 0–10V dimming output wiring. A Single Zone 0–10V
controller has one pair (violet and gray) of 0–10V output wires
(22 AWG). A Dual Zone 0–10V controller has a second pair of 0–10V
output wires (22 AWG): gray/white and violet/white.

a.

Connect the Zone 1 output wires, gray (-) and violet (+), to the
dimmed input of the connected load.

b.

For the Dual Zone 0-10V Controller, connect the Zone 2 output
wires, gray/white (-) and violet/white (+), to the dimmed input of
the second connected load.

2.

Reinstall the junction box cover plate.

CAUTION:

The 0–10V control outputs must be treated as NEC Class 1

control signals, in the same manner as other high voltage connections.

SmartSpace Controller–Gen 2

Page 9 of 12

Echoflex Solutions

Summary of Contents for Elaho SmartSpace Controller-Gen2

Page 1: ...2019 12 Overview The Elaho SmartSpace Controller Gen 2 provides fully rated 20 A relays for direct control of individual fixtures or zone power and offers fully isolated 0 10 V dimming control for com...

Page 2: ...onnect EchoConnect is a two wire topology free system that provides the SmartSpace Controller Gen 2 with the flexibility to connect in a system with up to 16 Elaho control products and up to 15 other...

Page 3: ...el supports Power input 120 277 VAC 60 Hz Load rating 20 A general purpose tungsten or resistive 16 A electronic ballast Dual Zone model supports Power input 120 277 VAC 60 Hz Load rating 20 A general...

Page 4: ...nect is a bidirectional protocol that uses one pair of wires data and data for both data and power Echoflex Solutions recommends using Belden 8471 or approved equal Class 2 wire The total combined len...

Page 5: ...osition d arr t et suivez les proc dures de Consignation D consignation prescrites par la norme NFPA 70E WARNING For indoor use only Must install to an electrical junction box or wireway AVERTISSEMENT...

Page 6: ...ire is pulled appropriately Terminate Cat5 wiring using the EchoConnect Cat5 Station Termination Kit and install it using a bus topology See the installation guide that is provided with the Cat5 Stati...

Page 7: ...re of the lighting load b Connect the black power input wire 12 AWG to the line input feed wire hot from the breaker panel 2 Connect the relay output wiring A Single Zone controller has one red relay...

Page 8: ...lack Green Yellow EchoConnect Ground Red Load 1 Red White Load 2 Occupancy Sensor 24 VDC 24 VDC Red Common Black Sensor Input Yellow Dual Zone SmartSpace Occupancy Sensor 24 VDC 24 VDC Red Common Blac...

Page 9: ...erre avant de raccorder tout c blage de commande 0 10V l appareil The 0 10V dimming output wiring exits the SmartSpace Controller Gen 2 through the top nipple of the enclosure with the power wiring 1...

Page 10: ...Zone model only do not set the Zone switch setting to a number higher than 15 If set to 16 both circuits in the controller will be assigned to and controlled on Zone 16 2 Set the Space rotary switch...

Page 11: ...ux Input Mode button to cycle through the available sensor types Troubleshooting Restore Defaults To return the SmartSpace Controller Gen 2 to factory defaults set both rotary switches to 16 and then...

Page 12: ...ert the microSD card in the SD slot on the side of the SmartSpace Controller Gen 2 enclosure The Dim Mode LED will illuminate amber in a triple blink pattern while the firmware is updating and then wi...

Reviews: