Echoflex Solutions Installation Guide
SmartSpace Controller–Gen 2
Prepare for Installation
The SmartSpace Controller–Gen 2 is designed for mounting directly to an
electrical junction box or panel (provided by others) at the electrical lighting
load, upstream of the load in the circuit.
Note:
If your installation requires Class 2 wiring to be installed in
separate conduit, a voltage barrier installation box is available from
Echoflex Solutions. Order Echoflex Solutions part number 7187A1000.
EchoConnect Control Wiring
The SmartSpace Controller–Gen 2 connects to the EchoConnect station
communication bus for control. EchoConnect is a bidirectional protocol that
uses one pair of wires (data + and data -) for both data and power. Echoflex
Solutions recommends using Belden 8471 (or approved equal) Class 2 wire.
The total combined length of an EchoConnect wire run (using Belden 8471, or
equal) may not exceed 500 m (1,640 ft).
Note:
All control wiring should be installed and terminated by a
qualified installer and should follow standard wiring installation practices.
Leave approximately 20 cm (8 in) of wiring in the back box for connection
and to allow slack for future service needs.
Note:
Echoflex Solutions requires that all Elaho stations and devices be
grounded for ESD protection. Pull an additional 2.5 mm
2
(14 AWG) wire
for grounding when control wires are not installed in grounded metal
conduit.
SmartSpace Controller–Gen 2
Page 4 of 12
Echoflex Solutions