Echoflex Solutions Installation Guide
SmartSpace Controller–Gen 2
Dimming
Ballast 1
Gray (-)
0–10 V
Violet (+)
Red
Load 1
White
Black
Green/Yellow
EchoConnect
Ground
Black 120–277 VAC
White Neutral
Black 120–277 VAC
White Neutral
Single Zone
SmartSpace
Dimming
Ballast 1
Gray (-)
0–10 V
Violet (+)
Gray/White (-)
0–10 V
Violet/White (+)
Dimming
Ballast 2
White
Black
Green/Yellow
EchoConnect
Ground
Red
Load 1
Red/White
Load 2
Occupancy
Sensor
(24 VDC)
24 VDC Red
Common Black
Sensor Input
Yellow
Dual Zone
SmartSpace
Occupancy
Sensor
(24 VDC)
24 VDC Red
Common Black
Sensor Input
Yellow
Connect Sensor Wiring
1.
Locate the sensor input wires on the side of the controller.
2.
Connect the red wire (22 AWG) to the 24 VDC red wire from the
sensor.
3.
Connect the black wire (22 AWG) to common.
4.
Connect the yellow wire (22 AWG) to the sensor control output.
SmartSpace Controller–Gen 2
Page 8 of 12