33
2.4 DERD Connection
DRED is used for Australia and New Zealand installation to support several demand response
modes.
Demond response
mode
Requirement
DRM0
Disconnected
Import power = 0 & Generate power = 0
DRM1
Import power = 0
DRM2
Import power < 50%
DRM3
Import power < 75%
DRM4
Import power = Not limited
DRM5
Generate power = 0
DRM6
Generate power < 50%
DRM7
Generate power < 75%
DRM8
Generate power = Not limited
●DRED terminal: