2.3 Cable Connection
2.3.1General
Make sure all the switches and breakers on the BESS are turned off.
Note: For Australia and New Zealand the PV SWITCH is not integrated.
Note: The external isolation devices for PV array ports shall include the requirement of an
additional external break switching device that conforms to the requirements AS/NZS 4777.1
2.3.2 Connect the Inverter Box and Battery Box
Recommended cables and terminals:
Cable Type
Cable Specification
Terminal Model
PE cable
10AWG
OT5-4
(In accessory)
PV+ cable
10AWG(RED)
Positive DC Plug
(In accessory)
PV- cable
10AWG(BLACK)
Negative DC Plug
(In accessory)
Grid cable
8AWG
E10-12
(In accessory)
EPS cable
10AWG
E6012
(In accessory)