H
oogkamerstraat 188, 9140 Temse Oos-Vlaanderen Belgium +32 470 80 80 83
11
⚠
A
lways start from connection number 1 and don’t skip connection
enumeration to avoid error in reading sensors. It’s also highly advised to use the
same type of sensors (choose all the sensors from SHT2x or SHT3x) to reduce
reading time and errors.
3.
Enable using Multiple sensors (see
).
4.
Edit the number of sensors you will connect and would like to read.
I2C repeater/ Line extender:
In case of longer bus length required to install your sensor far from the controller unit, we have
two solutions for a short range (5meters) and also long range (35meters). The installation and
wiring needs to be done following the type of the chosen option for your needs accordingly:
1.
I2CR (I2C bus repeater for maximum 5 meters length connection):