5 Installation
5.4 Mounting
48
MICRO PANEL XV400 5.7"/8.4"
12/2014 MN04802009Z-EN
www.eaton.com
3.1
Fit the seal in the groove on the rear of the device front plate.
3.2
Use a small screwdriver to push the securing tabs of the seal into the groove.
The securing tabs must not protrude over the edge of the groove.
The securing tabs must not point to the bottom of the groove.
4
Fit the supplied threaded pins in the retaining brackets beforehand.
5
Fit the device carefully from the front into the mounting cutout.
6
Clip on the retaining brackets in the recesses provided for them on the device as shown below and
fix the device by tightening the threaded pins until the front of the MICRO PANEL is flush with the
surface of the control cabinet at the fixing points.
Abb. 34 Seal fitted (detail shows optimum position of a securing tab (A))
Abb. 35 Threaded pin pre-fitted in a retaining bracket
CAUTION
Mechanical damage to the device
Tightening the threaded pins too tightly may damage the device.
Tighten threaded pins with a tightening torque of 0.25…0.3 Nm.
The positions of the retaining brackets depend on the mounting requirements.