30
EATON XSTORAGE COMPACT INSTALLATION MANUAL
P-164000907 - March 2022 www.eaton.com
00 Title
*Fuses are of the type gG and MCB tripping characteristics C.
5.4.3 Minimum recommended fuse sizes
Table 7 . AC input fuse and MCB ratings*
xStorage Compact
rating (kW/kVA)
10
20
30
40
Fuse / MCB rating [A]
20
40
63
80
5.5 Install a remote EPO switch
You can use a remote EPO switch in case of an emergency to shut down the ESS and remove power to the essential
load from a location away from where the ESS is installed.
EPO is connected to the ESS’s top front panel, on connector EPO. Figure 13: Connections of the EPO switch shows the
NO and NC connections of the EPO switch.
EPO connector (front view):
•
A = Normally open
•
B = Normally closed
Figure 13 . Connections of the EPO switch