4 Commissioning
4.1 Initial Commissioning
Compact PLC XC-152
05/17 MN050001ZU EN www.eaton.com
41
4.1.2 Connect Computer and XC-152 in the network
▶
Open Remote-Client on the computer and click on the "Detect" menu
option.
▶
Power up the XC-152 while pressing the CTRL button and hold the but-
ton down until the SF LED lights up green.
Information on the detected XC-152 will be displayed.
Variant a:
A DHCP server on the LAN will have assigned the XC-152 an IP address.
Variant b:
A prompt with a suggested IP address will be shown. Once you click on OK,
the XC-152 will be assigned this IP address.
▶
Click on OK to connect.
4.1.3 Connect Computer and XC-152 connected directly with a cable
▶
Configure the computer's network settings:
•
IP address: 192.168.1.2
•
Subnet mask: 255.255.255.0
▶
Power up the XC-152 and wait until the COM LED turns off.
▶
Open Remote-Client on the computer and
connect to the XC-152.
4.1.4 Setting the IP address with an SD card
You will need to create two files and save them in the SD card's root direc-
tory.
“autolaunch.inf” file with the following contents:
[autolaunch]
open = SetIpAddress.bat
RunOnBoot = 1
→
Condition:
There must not be a firewall blocking the DHCP ports.
→
Please note that the IP address assigned to the XC-152 is only
temporary.
→
Condition:
It must be possible to change the computer's IP address.
→
Condition:
SD card reader on computer.