background image

2

Xenon beacon - Xb10

   TM102.L   May 2022   www.eaton.com

Xenon beacon - XB10

English

3.0 Operation

The operating voltage of the unit is stated on the unit label. The beacon can be powered directly or initiated via a 

telephone ringing signal, depending on electronic configuration supplied.

General arrangement

Ex de VERSION

Ex e COVER SCREWS

2 POSITIONS

58±2mm

Ø

123.5±2mm

45°±0.5°

357±5mm

GLAND ENTRY
2 POSITIONS

84±2mm

85±2mm

50±2mm

35±1mm

17.5±1mm

FIXING HOLE

Ø

4.5±1mm

3 POSITIONS

299±4mm

227

±2mm

Ø

122±2mm

95±2mm

37±1mm

DO

NO

TO

VER-TIGHTE

NS

CREW

S

Ex

eT

ER

MI

N

AL

CH

A

M

B

E

R

Ex d VERSION

4.0 Maintenance

During the working life of the unit, it should require little 

or no maintenance. GRP will resist attack by most acids, 

alkalis and chemicals and is as resistant to concentrated 

acids and alkalis as most metal products. However, if 

abnormal or unusual environmental conditions occur due 

to plant damage or accident etc., then visual inspection 

is recommended. If the unit requires cleaning, then only 

clean exterior with a damp cloth to avoid electro-static 

charge build up.

The replacement of the xenon tube (see below) can be 

carried out by competent site personnel. Other repairs 

should be undertaken by returning the unit to MEDC.

If a unit fault should occur, then the unit can be repaired 

by MEDC. All parts of the unit are replaceable. If 

you acquired a significant quantity of units, then it is 

recommended that spares are also made available. 

Please discuss your requirements with the Technical Sales 

Engineers at MEDC.

During maintenance, if the cover/lens assembly grease 

needs to be re-applied, a PFPE (Perfluoropolyether) based 

grease such as Krytox GPL203 by DuPont or Perfluorolube 

22/6 by Performance Fluids Ltd should be used, to 

prevent damage to the O-ring.

Removing/replacing xenon tube

CAUTION: Before removing the cover assembly, 

ensure that the power to the unit is isolated.

ote: 

N

These units each contain two separate xenon tubes 

which should both be replaced at the same time. 

Unscrew the setscrew on the cover one full turn 

(2.0mm A/F hexagon key). Carefully unscrew and 

remove the cover assembly (using a 120mm hook 

wrench if required).

Remove the old tubes by unscrewing the terminal block 

fixings. The replacement xenon tubes can now be fitted 

(see the xenon tube installation sheet, which is supplied 

with the replacement tube).

To replace the cover, use the same procedure as above 

but in reverse manner, ensuring the cover is screwed 

down tightly and ensuring there is no damage to 

the thread surfaces or mating faces of the cover and 

enclosure. There should be a maximum gap of 0.2mm 

between the faces of the cover and enclosure to ensure 

correct o-ring compression and maintain the IP rating of 

the unit.

Summary of Contents for XB10

Page 1: ...Technical manual Xenon beacon XB10...

Page 2: ...URPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL...

Page 3: ...CTION 1 2 0 INSTALLATION 1 General 1 Cable termination 1 General 1 Exd unit 1 Exde unit 1 3 0 OPERATION 2 4 0 MAINTENANCE 2 Removing replacing xenon tube 2 5 0 CERTIFICATION APPROVALS 3 lECEx units 3...

Page 4: ...iv Xenon beacon XB10 TM102 L May 2022 www eaton com...

Page 5: ...for the equipment grounding connection and the external terminal is for a supplementary bonding connection where local codes or authorities permit or require such a connection Ensure there is not too...

Page 6: ...he unit can be repaired by MEDC All parts of the unit are replaceable If you acquired a significant quantity of units then it is recommended that spares are also made available Please discuss your req...

Page 7: ...le entry device unused with this apparatus must exceed 12mm in length II Painting and surface finishes other than those applied by the manufacturer are not permitted B Exde units Certificates BAS00ATE...

Page 8: ...ralit s 5 Connexion des c bles 5 G n ralit s 5 Unit Exd 5 Unit Ex de 5 3 0 FONCTIONNEMENT 6 4 0 MAINTENANCE 6 Retirer remplacer le tube x non 6 5 0 CERTIFICATION HOMOLOGATIONS 7 Unit s IECEx 7 Unit s...

Page 9: ...P quivalent celui du feu et tre int gr s l unit de fa on assurer le maintien de sa classification La borne interne de mise la terre doit tre utilis e pour mettre l quipement la terre La borne externe...

Page 10: ...l quipement celui ci peut tre r par par MEDC Toutes les pi ces sont rempla ables Lorsqu un nombre significatif d unit s ont t acquises il est recommand de disposer d unit s de rechange Les technico c...

Page 11: ...s BAS00ATEX2204X IECEx BAS 10 0086X I Le filtetage de contact de tout p riph rique d entr e de c ble inutilis avec cette appareil doit mesurer plus de 12mm II Toutes peintures ou finitions de surface...

Page 12: ...llgemeines 9 Kabelenden 9 Allgemeines 9 Exd ger t 9 Exde ger t 9 3 0 BETRIEB 10 4 0 WARTUNG 10 Entfernung Erneuerung der Xenon R hren 10 5 0 ZERTIFIZIERUNG GENEHMIGUNGEN 11 Iecex einheiten 11 ATEX Ein...

Page 13: ...endet werden und dass die Baugruppe korrekt verkleidet und geerdet ist Alle Kabeldurchf hrungen m ssen ber eine NEMA IP Einstufung verf gen die der des Blinklichts entspricht und in die Einheit integr...

Page 14: ...kaum oder gar keine Wartung Glasfaserverst rkter Kunststoff h lt den Angriffen der meisten S uren Alkalien und Chemikalien stand und ist wie die meisten Metalle widerstandsf hig gegen ber konzentriert...

Page 15: ...ild sind mit der ATEX Gruppe und der Kategorie Kennzeichnung versehen II 2 G Hierbei gilt Steht f r die ATEX Kompatibilit t II Steht f r die Eignung in Oberfl chenbranchen 2 Steht f r die Eignung in e...

Page 16: ...ontained in this document and to prices are reserved so are errors and omissions Only order confirmations and technical documentation by Eaton is binding Photos and pictures also do not warrant a spec...

Reviews: