23
Operation
EATON TFX INSTALLATION AND OPERATION MANUAL
6046279-001
September 2019
www.eaton.com
INFORMATION
The logfile is sent to the Data platform when its size
reaches 1 kB, irrespective of the
period set.
5.2.3.1 Receiving J1939 messages with the PGN 61444
In the following, the example of a J1939 message is used
to explain the general procedure for configuring CAN
reception messages.
The procedure can also be applied to other CAN messages
from other CAN protocols.
For detailed information on creating objects, see chapter
Creating object dictionary groups and objects.
CREATING A PGN 61444
1. Create the object dictionary group
C
ustom
C
an
C
ommuniCation
> r
eCeive
Can m
essages
(PDO
s
). Note
that your DOD file may already contain this.
2. In the object dictionary group
r
eCeive
Can m
essages
(PDOs), create a new object dictionary entry
r
eCeive
m
essages
PDO.
3. Rename the object
r
eCeive
m
essage
PDO as
pgn
61444.
RECEIVE MESSAGE COMMUNICATION PARAMETERS
4. Right click on the PGN 61444 folder and select the
C
ommuniCation
tab.
5. Set and save the following:
Table 16: Communication settings for PGN 61444
Description
Selection Function
v
aliD
o
n
Can
i
nterfaCe
Set
Enabling the configuration, defining the
CAN interface for reception (if several
are available).
CAN
p
rotoCol
None
The receive CAN message is a single
message (Layer 2). It is not treated according
to a superordinate CAN protocol.
TIMEOUT AND CONDITIONSS
6. Select the
t
imeout
anD C
onDitions
tab.
7. Set and save the following:
Table 17: Communications settings in PGN 61444 –
Timeout and conditions
Description
Selection
Function
a
lways
a
Ctive
Set
The CAN message is received
irrespective of events or conditions.