Behaviour of SmartWire-DT
modules DIL-SWD-32-…
115
02/11 MN05006002Z-EN
Table 24:
Diagnostics with the
Ready-LED
Switching on Contactors with DIL-SWD-32-001
The DIL-SWD-32-001 has no selector switch, thus the status
indicated by the Ready LED represents the actual switch
position of the contactor.
Switching on Contactors with DIL-SWD-32-002
The 1-0-A selector switch of the DIL-SWD-32-002 makes it
possible for the operator to electrically switch the contactor
on (position 1, confirm ON) and off (position 0, confirm OFF)
by hand. To activate the contactor via the SmartWire-DT
network the selector switch must be in position A (Auto-
matic).
Event
Explanation
Remedy
LED green
continuous
light
1)
Fault-free operation, data exchange
OK.
The DIL-SWD-32-… has received the
switching command
Off
for the
contactor.
LED orange
continuous
light
1)
Fault-free operation, data exchange
OK.
The DIL-SWD-32-… has received the
switching command
On
for the
contactor.
LED off
No 15 V DC device voltage via the
SmartWire-DT network or the DIL-
SWD-32-… or LED is defective.
Check the power supply or
DIL-SWD-32-….
LED green
flashing (1 Hz)
No data exchange with the Smart-
Wire-DT gateway
The DIL-SWD-32-… may not be in the
target configuration or the SmartWire-DT
gateway is just creating a target configu-
ration.
1) On the DILM module DIL-SWD-32-002 in manual mode (position 0 or 1) the actual switch position
of the contactor can deviate from the indicated switching command of the controller.
Only in position A and with a functioning SmartWire-DT network does the status indicated by the
Ready LED on the DIL-SWD-32-002 comply with the actual switch position of the contactor.
In the case of the DILM module DIL-SWD-32-001 the switch position of the contactor also complies
with the indicated switching command of the controller. An exception to this is the “Defect in the
case of an insufficient contactor supply”, see below.
www.comoso.com