SM65 Supervisory Module Handbook
16
Copyright © 2004-2009 Eaton Corporation. All Rights Reserved.
IPN 997-00012-35E December 2009
►
To restart shutdown rectifiers using DCTools
1
Start
DCTools
(refer to the Communications Options on page
2
From the
DCTools
System Summary (Home) screen, go to Rectifiers
.
3
Click on the
Restart ALL Rectifiers
button.
4
Click the
Apply Changes
button.
Manual Start Equalize
This function starts the Equalize control function (see details on page
), if conditions allow.
SM65 version 4.04 or later:
If there is an AC supply fail then Equalize will have the state
Pending
. Equalize will then start
when AC power is restored (unless Fast Charge is enabled then Equalize will start when the
Fast Charge is completed).
Use Reset Battery State to cancel a Pending Equalize. See details on page
.
Equalize will be active for the configured
Duration
or until it is stopped manually.
►
To manually start Equalize using the SM65 keypad
1
Press
:
to go to Status View Mode.
2
Press
6
until the display shows
Next Equalize ...
or
Manual Equalize Can Start
.
If the display shows
Equalize Disabled
then Equalize must be Enabled before it can be
started. Go to Configuration Mode to Enable.
3
Press
8
to start Equalize.
4
Equalize will operate for the configured
Duration
or press
8
to stop Equalize.
►
To manually start Equalize using DCTools
1
Start
DCTools
(refer to the Communications Options on page
2
Go to
Voltage Control
>
Equalize
.
3
Click on
Start
(Equalize must be
Enabled
).
4
Click
Apply Changes
.
5
Equalize will operate for the configured
Duration
or click on
Stop
then
Apply Changes
to
stop Equalize.