System Operation
Copyright © 2008-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-63C August 2011
35
Parameter
Description
Where to find:
Battery Charge
Over Current
Threshold
Battery Charge Over Current alarm is activated if the
battery charge current is above this percentage of the
battery capacity or 2A, which ever is greater.
DCTools: Alarms > Alarm
Configuration
Auxiliary
Temperature Low
Threshold*
Auxiliary Temperature Low alarm is activated if the
auxiliary temperature is below this value.
Auxiliary
Temperature Low
Hysteresis*
The hysteresis that is applied before the alarm
deactivates.
Auxiliary
Temperature High
Threshold*
Auxiliary Temperature High alarm is activated if the
auxiliary temperature is above this value.
Auxiliary
Temperature High
Hysteresis*
The hysteresis that is applied before the alarm
deactivates.
In Discharge Alarm
Condition
Set to indicate when In Discharge alarm will activate -
Always
or
Only While AC Present
.
In Discharge Alarm
Threshold
In Discharge alarm is activated if the battery current is
above this percentage of the battery capacity.
* See Auxiliary Temperature Disconnect on page
System Overload Alarm
The System Overload alarm activates if the total system load exceeds a percentage of the
installed rectifier capacity for a specified period. This indicates that additional rectifiers need to
be installed. This is useful at sites where there is ongoing installation of additional load
equipment.
► To enable System Overload
In DCTools go to:
Alarms
>
Alarm States
. Enable and configure
System Overload
alarm. See
System Alarm Configuration on page
Go to:
Alarms
>
Alarm Configuration
. Configure the
System Overload
alarm parameters. See
details on page
Information
The following information is available about System Overload.
Parameter
Description
Where to find:
System Power
The output power of the system as a percentage
of the total nominal power the system is capable
of supplying.
SC100: Analogs
DCTools: Analog Inputs