SC100 Handbook
20
Copyright © 2008-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-63C August 2011
Configuration
Set the following parameters.
Parameter
Description
Where to find:
Voltage
The bus voltage maintained during a Fast Charge. Use
the value recommended by the battery manufacturer.
SC100: Menu >
Configuration > Fast
Charge > Edit
DCTools: Control Processes
> Fast Charge
Voltage Threshold If the bus voltage drops below this value during an ac
supply failure, then
Fast Charge
starts when the ac
supply is restored.
Fast charge
can also be started based
on the
Ah Threshold
.
DCTools: Control Processes
> Fast Charge
Ah Threshold
If
Ah Discharged
exceeds this value during an ac supply
failure, then
Fast Charge
starts when the ac supply is
restored. The threshold is given as a percentage of
installed C10 battery capacity.
Fast charge
can also be
started based on the
Voltage Threshold
.
Maximum
Duration
The maximum duration of a
Fast Charge.
Use the value
recommended by the battery manufacturer.
Recharge
Percentage (%)
The ratio of ampere-hours recharged to the ampere-
hours discharged.
Fast Charge
stops either when the Ah
recharged equals the Ah discharged x
Fast Charge
Recharge Percentage
, or after
Maximum Duration
.
Battery Capacity
Set to the rated 10 hour capacity of the installed battery
strings. Zero means no battery is installed.
SC100: Menu >
Configuration > System >
Edit > Battery Capacity
>Edit
DCTools: Batteries
Reset Battery State
The SC100 monitors battery discharge and maintains a value called
Ah Discharged
. In a new
SC100
Ah Discharged
is set to zero. During operation of the dc power system the value is
increased as the battery is discharged, and reduced as the battery is recharged.
The value of
Ah Discharged
is used to start the
Fast Charge
control process. See details on page
► To view current value of Ah Discharged
In DCTools go to: Batteries.
If a battery or the SC100 is changed, then reset the value of
Ah Discharged
to zero (when the
battery is fully charged).
► To set the value of Ah Discharged back to zero
In DCTools go to: Batteries. Click Reset Battery State.
Any active or pending Fast Charge or Equalize will be cancelled.
Summary of Contents for SC100
Page 52: ......