LBRS Test
The
LBRS Test
function will cycle the rectifiers once.
LBRS Test is not available if LBRS is
Disabled
,
Suspended
or
Inactive. If
Battery Test Before
LBRS is enabled then a Battery Test will be performed (see details on page
► To start an LBRS Test
Configure and
Enable
LBRS (see details on page
In DCTools go to:
Rectifiers
>
Load Based Rectifier Shutdown
>
LBRS Test
.
Set
LBRS Restart After Test
to the required setting.
When the test is completed or stopped normal LBRS operation will start after this delay.
When LBRS is
Active
, click
Start
.
LBRS Test will cycle the available rectifiers with a cycle time of 90 seconds until all rectifiers
have been shutdown and restarted.
If required, click
Stop
to end an
LBRS Test
before all rectifiers have been shutdown and
restarted.
LBRS Suspend
If required, when LBRS is active it can be temporarily suspended for system maintenance or
other reasons.
LBRS Suspend is not available if LBRS is
Disabled
,
Testing
or
Inactive.
► To temporarily suspend LBRS
In DCTools go to:
Rectifiers
>
Load Based Rectifier Shutdown
>
LBRS Suspend
.
Set
LBRS Restart
to the required setting.
Normal LBRS operation will start after this delay.
When LBRS is
Active
, click
Suspend
.
LBRS
will be suspended and all shutdown rectifiers will restart.
Normal LBRS operation will resume automatically after the
LBRS Restart
delay. Or, click
Resume.
LBRS is automatically suspended if the Battery Fuse Fail alarm is active.
Auxiliary Temperature Shutdown
This feature requires a second temperature sensor connected to the I/O board.
All rectifiers can be shutdown if the temperature measured by the Auxiliary Temperature
sensor is outside a configured range.
If a sensor used for Auxiliary Temperature Shutdown becomes faulty or disconnected this
may cause an unnecessary rectifier shutdown.
See also LVD Auxiliary Temperature Disconnect on page