System Alarm Configuration
The following system alarm parameters can be configured.
Parameter
Description
Where to find:
Severity
Set to
Disabled
if no indication is required when the
alarm is active. Or, set to the required alarm priority.
See details on page
DCTools: Alarms > Alarm
State
DO Mapping A
If required, select a digital output (relay) that will be
operated when the alarm is active.
DO Mapping B
If required, select a second digital output (relay) that
will be operated when the alarm is active.
AC Fail
Recognition Period
An ac supply failure condition must be continuously
active for this period before an AC Fail alarm is
generated.
DCTools: Alarms > Alarm
Configuration
Enable High Float
Tracking
The High Float alarm threshold will be adjusted when
the operating voltage is changed by a voltage control
process.
High Float
Threshold
High Float alarm is activated if the bus voltage is
above this value.
Enable Low Float
Tracking
The Low Float alarm threshold will be adjusted when
the operating voltage is changed by a voltage control
process.
Low Float
Threshold
Low Float alarm is activated when the bus voltage is
below this value.
High Load
Threshold
High Load alarm is activated if the bus voltage is
above this value.
Low Load
Threshold
Low Load alarm is activated if the bus voltage is below
this value.
Battery Fuse Fail
Active State
Specifies if the alarm activates from an open or closed
contact.
Battery
Temperature High
Threshold
Battery Temperature High alarm is activated if the
battery temperature is above this value.
Battery
Temperature Low
Threshold
Battery Temperature Low alarm is activated if the
battery temperature is below this value.
System Overload
Type
See details on page
System Overload
Recognition Period
See details on page
System Overload
Threshold
See details on page
AC High Threshold AC High alarm is activated if the ac voltage is above
this value.
AC Low Threshold AC Low alarm is activated if the ac voltage is below
this value.