Instructional Booklet

Effective: June 2007

Page

 

3

Instruction Manual for the Eaton RTC-50 

Automatic Transfer Switch Controller

A standard RTC-50 controller will:

Monitor Utility and Generator power source voltages 

Provide undervoltage protection of the Utility and Generator 

power sources

Permit easy customer set-up

Provide source status indications

Provide remote indication that generator maintenance needs to 

be performed

1.4 Glossary

With respect to their use within this document and as they relate 

to transfer switch and controller operation, the following terminol-

ogy is defined.

Available

A source is defined as “available” when it is within its undervolt-

age setpoint range.

Connected

Connected is defined as when the input is shorted by an external 

contact or connection.

Failed or Fails

A source is defined as “failed” when it is outside of the applicable 

voltage ranges for the nominal voltage and for a time exceeding 

0.5 seconds after the time delay emergency fail (TDEF) time 

delays expires.

Failsafe

Failsafe is a feature that prevents disconnection from the only 

available power source and also forces a transfer or re-transfer 

operation to the only available power source.

Re-Transfer

Re-transfer is defined as a change of the load connection from the 

Generator to the Utility.

Utility

Utility is the primary source (normal source, normal power source, 

or normal).

Generator

Generator is the secondary source (emergency source, emergency 

power source, emergency, standby, or backup source).

Utility: Failed or Fails

Utility is defined as “failed” when it is outside of its undervoltage 

setpoint range.

Generator: Failed or Fails

Generator is defined as “failed” when it is outside of its undervolt-

age setpoint range for a time exceeding 0.5 seconds after the 

TDEF time delay expires.

Transfer

Transfer is defined as a change of the load connection from the 

Utility to the Generator power source.

Unconnected

Unconnected is defined as when the input is not shorted by an 

external contact or connection.

1.5 Functions/Features

The primary function of RTC-50 controller is to accurately monitor 

the Utility and Generator power sources and provide the necessary 

intelligence to operate the ATS in an appropriate and timely man-

ner.  In addition, the RTC-50 controller provides status information 

through on-board and remote indicators.

The following is a list of the features of the RTC-50 controller.

1.

Time Delay Normal to Emergency (TDNE)

This feature provides a time delay when transferring from the 

Utility to the Generator power source.  Timing begins when 

the Generator becomes available.  It permits controlled trans-

fer of the load circuit to the Generator.

Jumper selectable at 20 or 50 seconds.  Default is 20 sec-

onds.

3.

Time Delay Emergency to Normal (TDEN)

This feature provides a time delay of the re-transfer operation 

to permit stabilization of the Utility source.  Timing begins 

when the Utility becomes available.  If the Generator fails 

during timing, then re-transfer is delayed for up to 6 seconds 

to allow the Generator to recover.

Fixed setting of 10 seconds

5.

Generator Monitoring and Protection

This feature provides monitoring and protection based on the 

Generator voltage setpoints.  All feature 5 functions are fail-

safe operations.

5J. All Phase Undervoltage Protection

Dropout: 168 Vac (70% of 240 Vac nominal)

Pickup:   192 Vac (80% of 240 Vac nominal)

7.

Time Delay Emergency Fail (TDEF)

This feature provides a time delay that prevents a connected 

Generator source from being declared “failed” in order to 

override momentary generator fluctuations.  If the Generator 

remains in the failed state then, after the TDEF timer expires, 

the transfer switch will proceed with the programmed 

sequence for re-transfer.  

Fixed setting of 6 Seconds

12. Power Source Annunciation

This feature provides LEDs to indicate power source availabil-

ity.

12G.  Utility - Available

This feature provides a green LED that, when lit, indicates 

that the Utility is available.

12H.  Generator - Available

This feature provides a red LED that, when lit, indicates that 

the Generator is available.

15M.  Load Shed

Two sets of contacts are available and can be used to control 

large connected loads on the Generator (i.e. air conditioners, 

hot tubs, etc.).  The contacts are rated for 250 Vac, 5 amps.

Summary of Contents for RTC-50

Page 1: ...tion Manual for the Eaton RTC 50 Automatic Transfer Switch Controller Instructional Booklet New Information Description Page 1 Introduction 2 2 Hardware Description 4 3 Operation 6 4 Programming 7 5 T...

Page 2: ...y trans fers back to the Utility and the Generator will shut down after a time delay ATSs automatically perform the transfer function and include three basic elements 1 Main contacts to connect and di...

Page 3: ...connection 1 5 Functions Features The primary function of RTC 50 controller is to accurately monitor the Utility and Generator power sources and provide the necessary intelligence to operate the ATS i...

Page 4: ...arize the reader with the RTC 50 controller hardware its nomenclature and to list the unit s specifications 2 2 LED Indicators Utility Available The green Utility Available LED illuminates if the util...

Page 5: ...tor light to indicate that routine maintenance is required for every 25 hours that the generator has run This will constitute one maintenance cycle The RTC 50 will keep track of the number of hours th...

Page 6: ...e falls below the 70 dropout level When the Generator source meets the requirements to be consid ered available the TDNE Time Delay Normal to Emergency timer will start timing TDNE is jumper programma...

Page 7: ...equency of either 50 or 60 hertz Figure 2 RTC 50 Programming Jumpers Table 2 is a summary of the Fixed and Jumper selectable settings that are available in the RTC 50 Table 2 Fixed and Jumper Selectab...

Page 8: ...Step 3 Disconnect the wires connected to J7 and J8 Step 4 Remove the four 4 screws located at the corners of the controller that secure it to the power panel Remove the controller Step 5 Align the ne...

Page 9: ...ility is available Is Generator available N ATS connects to Utility Utility Close Output closes TDNE timer times out 20 sec or 50 sec Transfer to Generator Gen Close Output closes Y Generator is power...

Page 10: ...For more information visit www eaton com IB00405004E 70 8664 Instructional Booklet Page 10 Effective June 2007 Instruction Manual for the Eaton RTC 50 Automatic Transfer Switch Controller Notes...

Page 11: ...IB00405004E 70 8664 For more information visit www eaton com Instructional Booklet Effective June 2007 Page 11 Instruction Manual for the Eaton RTC 50 Automatic Transfer Switch Controller Notes...

Page 12: ...between the purchaser and Eaton NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WAR RANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MER CHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE...

Page 13: ...para el con trolador RTC 50 del interruptor de transferencia autom tica Eaton Folleto instructivo Nueva informaci n Descripci n P gina 1 Introducci n 2 2 Descripci n del equipo 4 3 Operaci n 6 4 Prog...

Page 14: ...cuando hay dis ponible suficiente voltaje en el mismo Cuando la fuente de energ a del servicio es restaurada el ATS autom ticamente trans fiere nuevamente al servicio y el generador se interrumpe des...

Page 15: ...carga desde el servicio hacia la fuente de alimentaci n del generador Desconectado Se define desconectado cuando la entrada no est sometida a cortocircuito por un contacto o conexi n externos 1 5 Func...

Page 16: ...Indicadores con diodos emisores de luz LED Servicio disponible El diodo emisor de luz verde de disponibilidad del servicio se ilu mina si la fuente de alimentaci n del servicio cumple con los requisi...

Page 17: ...la luz indicadora del ser vicio del generador para indicar que se requiere un mantenimiento de rutina por cada 25 horas de funcionamiento del generador Esto constituir un ciclo de mantenimiento El RTC...

Page 18: ...cumple con los requisitos para ser considerada disponible el cronometraje del tiempo de demora de normal a emergencia TDNE comenzar a contar El TDNE es programable en 20 50 segundos La selec ci n de...

Page 19: ...a de 50 60 Hz Figura 2 Puentes para programaci n del RTC 50 La tabla 2 es un resumen de las selecciones fijas y seleccionables con puente que se encuentran disponibles en el RTC 50 Tabla 2 Selecciones...

Page 20: ...esquinas del controlador que lo aseguran al panel de energ a Quite el controlador Paso 5 Alinee el nuevo controlador con los agujeros de montaje Asegure el nuevo tablero del controlador utilizando la...

Page 21: ...a salida del servicio cerrado se cierra El TDNE demora del tiempo de normal a emergencia se interrumpe 20 50 segundos Transferencia al generador La salida del generador cerrado se cierra El generador...

Page 22: ...informaci n visite www eaton com IB00405004E 70 8664 Folleto instructivo P gina 10 Efectivo Junio 2007 Manual de instrucciones para el controlador RTC 50 del interruptor de transferencia autom tica E...

Page 23: ...E 70 8664 Para mayor informaci n visite www eaton com Folleto instructivo Efectivo Junio 2007 P gina 11 Manual de instrucciones para el controlador RTC 50 del interruptor de transferencia autom tica E...

Page 24: ...entre el com prador y Eaton NINGUNA GARANT A EXPRESA O IMPL CITA INCLUYENDO GARANT AS DE APTITUD PARA UN PROP SITO EN PARTICU LAR O APTITUD COMERCIAL O GARANT AS QUE SURJAN DEL CURSO DEL TRATO O USO...

Page 25: ...emploi de la commande RTC 50 pour commutateur de transfert automatique 50 Eaton Livret d instructions Nouveau document Sommaire Page 1 Introduction 2 2 Description du mat riel 4 3 Fonctionnement 6 4 P...

Page 26: ...e nouveau au r seau de distribution lectrique Un syst me intelligent active le transfert lorsque le courant sect eur est coup ou devient inf rieur une tension pr r gl e Un d marrage de moteur est alor...

Page 27: ...r des valeurs de r glage pour les sous tensions pour une dur e d pas sant de 0 5 seconde le point d expiration de la dur e de temporisa tion d urgence TDEF Transfert Changement du branchement de la ch...

Page 28: ...la commande RTC 50 ses pi ces et ses caract ristiques 2 2 Voyants DEL Disponibilit du courant secteur Le voyant DEL vert de courant secteur disponible s illumine lor sque la source de courant secteur...

Page 29: ...ecte le nombre d heures de fonctionne ment de la g n ratrice Apr s 25 heures de marche elle allume le voyant pour indiquer le besoin d entretien p riodique Ceci con stitue un cycle d entretien La comm...

Page 30: ...ratrice satisfait aux conditions exig es de disponibilit la temporisation de normal secours TDNE d bute la temporisation est programmable par cavalier 20 ou 50 secondes Le r glage 50 secondes peut tr...

Page 31: ...TC 50 Le tableau 2 est un r sum des r glages fixes et choisir avec cavaliers dans la commande RTC 50 Tableau 2 R glages fixes et choisir avec cavaliers DESCRIPTION VALEURS VALEUR PAR D FAUT USINE FIXE...

Page 32: ...fils reli s aux prises J7 et J8 tape 4 D posez les quatre 4 vis situ es aux coins de la com mande pour la fixer sur le panneau lectrique D posez la commande tape 5 Alignez la nouvelle commande sur le...

Page 33: ...ecteur la sortie de fermeture du courant secteur se ferme Temporisation de normal secours TDNE 20 ou 50 secondes Transfert vers la g n ratrice la sortie de fermeture du courant de g n ratrice se ferme...

Page 34: ...mples renseignements visitez www eaton com IB00405004E 70 8664 Livret d instructions Page 10 En vigueur d s juin 2007 Mode d emploi de la commande RTC 50 pour commutateur de transfert automatique 50 E...

Page 35: ...8664 Pour de plus amples renseignements visitez www eaton com Livret d instructions En vigueur d s juin 2007 Page 11 Mode d emploi de la commande RTC 50 pour commutateur de transfert automatique 50 E...

Page 36: ...LES GARANTIES MANANT DE CONDUITES HABITU ELLES OU D USAGE COMMERCIAL N EST TABLIE PAR RAPPORT AUX INFORMATIONS RECOMMANDATIONS ET DESCRIPTIONS CONTENUES DANS CE DOCUMENT Eaton ne peut en aucun cas tr...

Reviews: