background image

For more information visit: www.eaton.com

IB00405004E-70-8664

Instructional Booklet

Page

 

2

Effective: June 2007

Instruction Manual for the Eaton RTC-50

Automatic Transfer Switch Controller

SECTION 1:  INTRODUCTION

1.1  Preliminary Comments and Safety Precautions

This technical document is intended to cover all aspects associ-

ated with the installation, application, operation, and maintenance 

of the Automatic Transfer Switch Controller (RTC-50).  It is pro-

vided as a guide for authorized and qualified personnel only in the 

selection and application of the RTC-50 controller.  Please refer to 

the specific WARNING and CAUTION in Section 1.1.2 before pro-

ceeding.  If further information is required by the purchaser regard-

ing a particular installation, application, or maintenance activity, 

please contact an authorized Eaton Electrical Sales Representative 

or the installing contractor.

1.1.1 Warranty and Liability Information

No warranties, expressed or implied, including warranties of fit-

ness for a particular purpose of merchantability, or warranties aris-

ing from course of dealing or usage of trade, are made regarding 

the information, recommendations and descriptions contained 

herein.  In no event will Eaton be responsible to the purchaser or 

user in contract, in tort (including negligence), strict liability or 

otherwise for any special, indirect, incidental or consequential 

damage or loss whatsoever, including but not limited to damage or 

loss of use of equipment, plant or power system, cost of capital, 

loss of power, additional expenses in the use of existing power 

facilities, or claims against the purchaser or user by its customers 

resulting from the use of the information and descriptions con-

tained herein.

1.1.2 Safety Precautions

All safety codes, safety standards, and/or regulations must be 

strictly observed in the installation, operation, and maintenance of 

this device.

1.2 General Information

Automatic Transfer Switches (ATS) are used to protect critical 

electrical loads against loss of power.  The load’s Utility power 

source is backed up by an alternate power source such as a Gen-

erator.   An ATS is connected to both the Utility and Generator 

power sources and supplies the load with power from one of the 

two sources.  In the event that power is lost from Utility, the ATS 

transfers the load to the Generator power source.  Once Utility 

power is restored, the load is automatically transferred back to the 

Utility power source.
An intelligence system initiates the transfer when the Utility 

power fails or falls below a preset voltage.  An engine start is then 

initiated by the Generator and the ATS transfers to the Generator 

power source when sufficient Generator voltage is available.  

When the Utility power is restored, the ATS automatically trans-

fers back to the Utility and the Generator will shut down after a 

time delay.  
ATSs automatically perform the transfer function, and include 

three basic elements:

1. Main contacts to connect and disconnect the load to and from 

the power sources.

2. Solenoids to make the transfer of the main contacts from 

source to source.

3. Intelligence/supervisory circuits to constantly monitor the con-

dition of the power sources and thus provide the intelligence 

necessary for the switch and related circuit operation.

This manual deals with the third basic element of the ATS, the 

required intelligence/supervisory circuits.  The RTC-50 controller 

advances the application of intelligence, supervisory, and pro-

gramming capabilities for ATS equipment.

1.3 Product Overview

The RTC-50 controller is a comprehensive, multi-function, micro-

processor-based ATS controller.  Designed to meet the needs of 

markets worldwide, the RTC-50 controller:

Is a UL Listed Component

Complies with UL 1008/ CSA 22.2-178

Complies with UL 991 environmental tests

Complies with IEC 61000-4-2, 61000-4-3, 61000-4-4, 61000-

4-5, 61000-4-6, and 61000-4-11

Complies with CISPR 11, Class B

Complies with FCC Part 15, Class B

Meets European Standards Conformance (CE mark)

The RTC-50 controller provides an unmatched degree of pro-

grammed flexibility to address the needs of any system.  It oper-

ates on 240 VAC, single-phase at 50 or 60 Hz.  The RTC-50 

controller monitors the condition of the line voltage of both the 

Utility and Generator power sources.  The RTC-50 controller pro-

vides the necessary intelligence to insure that the transfer switch 

operates properly through a series of programmed sensing and 

timing functions.

 

CAUTION

ALL POSSIBLE CONTINGENCIES THAT MAY ARISE DURING INSTAL-

LATION, OPERATION, OR MAINTENANCE, AND ALL DETAILS AND 

VARIATIONS OF THIS EQUIPMENT DO NO PURPORT TO BE COV-

ERED BY THESE INSTRUCTIONS.  IF FURTHER INFORMATION IS 

DESIRED BY THE PURCHASER REGARDING A PARTICULAR INSTAL-

LATION, OPERATION, OR MAINTENANCE OF PARTICULAR EQUIP-

MENT, PLEASE CONTACT AN AUTHORIZED EATON ELECTRICAL 

SALES REPRESENTATIVE OR THE INSTALLING CONTRACTOR.

 

WARNING

THE WARNINGS AND CAUTIONS INCLUDED AS PART OF THE PRO-

CEDURAL STEPS IN THIS DOCUMENT ARE FOR PERSONNEL SAFETY 

AND PROTECTION OF EQUIPMENT FROM DAMAGE.  AN EXAMPLE 

OF A TYPICAL WARNING LABEL HEADING IS SHOWN ABOVE TO 

FAMILIARIZE PERSONNEL WITH THE STYLE OF PRESENTATION.  

THIS WILL HELP TO INSURE THAT PERSONNEL ARE ALERT TO 

WARNINGS, WHICH APPEAR THROUGHOUT THE DOCUMENT.  IN 

ADDITION, WARNINGS AND CAUTIONS ARE ALL UPPER CASE AND 

BOLDFACE.

 

WARNING

COMPLETELY READ AND UNDERSTAND THE MATERIAL PRESENTED 

IN THIS DOCUMENT BEFORE ATTEMPTING INSTALLATION, OPERA-

TION, OR APPLICATION OF THE EQUIPMENT.  IN ADDITION, ONLY 

QUALIFIED PERSONS SHOULD BE PERMITTED TO PERFORM ANY 

WORK ASSOCIATED WITH THIS EQUIPMENT.  ANY WIRING 

INSTRUCTIONS PRESENTED IN THIS DOCUMENT MUST BE FOL-

LOWED PRECISELY.  FAILURE TO DO SO COULD CAUSE PERMA-

NENT EQUIPMENT DAMAGE.

Summary of Contents for RTC-50

Page 1: ...tion Manual for the Eaton RTC 50 Automatic Transfer Switch Controller Instructional Booklet New Information Description Page 1 Introduction 2 2 Hardware Description 4 3 Operation 6 4 Programming 7 5 T...

Page 2: ...y trans fers back to the Utility and the Generator will shut down after a time delay ATSs automatically perform the transfer function and include three basic elements 1 Main contacts to connect and di...

Page 3: ...connection 1 5 Functions Features The primary function of RTC 50 controller is to accurately monitor the Utility and Generator power sources and provide the necessary intelligence to operate the ATS i...

Page 4: ...arize the reader with the RTC 50 controller hardware its nomenclature and to list the unit s specifications 2 2 LED Indicators Utility Available The green Utility Available LED illuminates if the util...

Page 5: ...tor light to indicate that routine maintenance is required for every 25 hours that the generator has run This will constitute one maintenance cycle The RTC 50 will keep track of the number of hours th...

Page 6: ...e falls below the 70 dropout level When the Generator source meets the requirements to be consid ered available the TDNE Time Delay Normal to Emergency timer will start timing TDNE is jumper programma...

Page 7: ...equency of either 50 or 60 hertz Figure 2 RTC 50 Programming Jumpers Table 2 is a summary of the Fixed and Jumper selectable settings that are available in the RTC 50 Table 2 Fixed and Jumper Selectab...

Page 8: ...Step 3 Disconnect the wires connected to J7 and J8 Step 4 Remove the four 4 screws located at the corners of the controller that secure it to the power panel Remove the controller Step 5 Align the ne...

Page 9: ...ility is available Is Generator available N ATS connects to Utility Utility Close Output closes TDNE timer times out 20 sec or 50 sec Transfer to Generator Gen Close Output closes Y Generator is power...

Page 10: ...For more information visit www eaton com IB00405004E 70 8664 Instructional Booklet Page 10 Effective June 2007 Instruction Manual for the Eaton RTC 50 Automatic Transfer Switch Controller Notes...

Page 11: ...IB00405004E 70 8664 For more information visit www eaton com Instructional Booklet Effective June 2007 Page 11 Instruction Manual for the Eaton RTC 50 Automatic Transfer Switch Controller Notes...

Page 12: ...between the purchaser and Eaton NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WAR RANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MER CHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE...

Page 13: ...para el con trolador RTC 50 del interruptor de transferencia autom tica Eaton Folleto instructivo Nueva informaci n Descripci n P gina 1 Introducci n 2 2 Descripci n del equipo 4 3 Operaci n 6 4 Prog...

Page 14: ...cuando hay dis ponible suficiente voltaje en el mismo Cuando la fuente de energ a del servicio es restaurada el ATS autom ticamente trans fiere nuevamente al servicio y el generador se interrumpe des...

Page 15: ...carga desde el servicio hacia la fuente de alimentaci n del generador Desconectado Se define desconectado cuando la entrada no est sometida a cortocircuito por un contacto o conexi n externos 1 5 Func...

Page 16: ...Indicadores con diodos emisores de luz LED Servicio disponible El diodo emisor de luz verde de disponibilidad del servicio se ilu mina si la fuente de alimentaci n del servicio cumple con los requisi...

Page 17: ...la luz indicadora del ser vicio del generador para indicar que se requiere un mantenimiento de rutina por cada 25 horas de funcionamiento del generador Esto constituir un ciclo de mantenimiento El RTC...

Page 18: ...cumple con los requisitos para ser considerada disponible el cronometraje del tiempo de demora de normal a emergencia TDNE comenzar a contar El TDNE es programable en 20 50 segundos La selec ci n de...

Page 19: ...a de 50 60 Hz Figura 2 Puentes para programaci n del RTC 50 La tabla 2 es un resumen de las selecciones fijas y seleccionables con puente que se encuentran disponibles en el RTC 50 Tabla 2 Selecciones...

Page 20: ...esquinas del controlador que lo aseguran al panel de energ a Quite el controlador Paso 5 Alinee el nuevo controlador con los agujeros de montaje Asegure el nuevo tablero del controlador utilizando la...

Page 21: ...a salida del servicio cerrado se cierra El TDNE demora del tiempo de normal a emergencia se interrumpe 20 50 segundos Transferencia al generador La salida del generador cerrado se cierra El generador...

Page 22: ...informaci n visite www eaton com IB00405004E 70 8664 Folleto instructivo P gina 10 Efectivo Junio 2007 Manual de instrucciones para el controlador RTC 50 del interruptor de transferencia autom tica E...

Page 23: ...E 70 8664 Para mayor informaci n visite www eaton com Folleto instructivo Efectivo Junio 2007 P gina 11 Manual de instrucciones para el controlador RTC 50 del interruptor de transferencia autom tica E...

Page 24: ...entre el com prador y Eaton NINGUNA GARANT A EXPRESA O IMPL CITA INCLUYENDO GARANT AS DE APTITUD PARA UN PROP SITO EN PARTICU LAR O APTITUD COMERCIAL O GARANT AS QUE SURJAN DEL CURSO DEL TRATO O USO...

Page 25: ...emploi de la commande RTC 50 pour commutateur de transfert automatique 50 Eaton Livret d instructions Nouveau document Sommaire Page 1 Introduction 2 2 Description du mat riel 4 3 Fonctionnement 6 4 P...

Page 26: ...e nouveau au r seau de distribution lectrique Un syst me intelligent active le transfert lorsque le courant sect eur est coup ou devient inf rieur une tension pr r gl e Un d marrage de moteur est alor...

Page 27: ...r des valeurs de r glage pour les sous tensions pour une dur e d pas sant de 0 5 seconde le point d expiration de la dur e de temporisa tion d urgence TDEF Transfert Changement du branchement de la ch...

Page 28: ...la commande RTC 50 ses pi ces et ses caract ristiques 2 2 Voyants DEL Disponibilit du courant secteur Le voyant DEL vert de courant secteur disponible s illumine lor sque la source de courant secteur...

Page 29: ...ecte le nombre d heures de fonctionne ment de la g n ratrice Apr s 25 heures de marche elle allume le voyant pour indiquer le besoin d entretien p riodique Ceci con stitue un cycle d entretien La comm...

Page 30: ...ratrice satisfait aux conditions exig es de disponibilit la temporisation de normal secours TDNE d bute la temporisation est programmable par cavalier 20 ou 50 secondes Le r glage 50 secondes peut tr...

Page 31: ...TC 50 Le tableau 2 est un r sum des r glages fixes et choisir avec cavaliers dans la commande RTC 50 Tableau 2 R glages fixes et choisir avec cavaliers DESCRIPTION VALEURS VALEUR PAR D FAUT USINE FIXE...

Page 32: ...fils reli s aux prises J7 et J8 tape 4 D posez les quatre 4 vis situ es aux coins de la com mande pour la fixer sur le panneau lectrique D posez la commande tape 5 Alignez la nouvelle commande sur le...

Page 33: ...ecteur la sortie de fermeture du courant secteur se ferme Temporisation de normal secours TDNE 20 ou 50 secondes Transfert vers la g n ratrice la sortie de fermeture du courant de g n ratrice se ferme...

Page 34: ...mples renseignements visitez www eaton com IB00405004E 70 8664 Livret d instructions Page 10 En vigueur d s juin 2007 Mode d emploi de la commande RTC 50 pour commutateur de transfert automatique 50 E...

Page 35: ...8664 Pour de plus amples renseignements visitez www eaton com Livret d instructions En vigueur d s juin 2007 Page 11 Mode d emploi de la commande RTC 50 pour commutateur de transfert automatique 50 E...

Page 36: ...LES GARANTIES MANANT DE CONDUITES HABITU ELLES OU D USAGE COMMERCIAL N EST TABLIE PAR RAPPORT AUX INFORMATIONS RECOMMANDATIONS ET DESCRIPTIONS CONTENUES DANS CE DOCUMENT Eaton ne peut en aucun cas tr...

Reviews: