background image

Eaton Remote Monitoring Device (RMD) Installation and Operation Manual P-164000516—Rev 02

5

O

Oppeerraattiioonn

This section describes how to operate the RMD.

R

RM

MD

D C

Coom

mppoonneennttss

The components identified and described in this section are used to connect and operate the RMD.

4.3” Display Screen

– shows UPS status

Power Pushbutton

– turns the RMD on (press and hold for 3 seconds) and off (press and hold for

11 seconds) and is used to silence the audible alarm

Audible Alarm

– the alarm sounds to alert an operator that an event needing attention is taking place. To

silence the audible alarm, press the power button momentarily (see )

Micro USB Connector

– connects the external charger to RMD internal battery

Ethernet Connector

– connects the RMD to the UPS PXG card

shows the location of the RMD components.

D

Diissppllaayy S

Sccrreeeenn S

Seeccttiioonnss

The display consists of two sections, a status indicator section on the left side of the screen and an information
area to the right of the status indicators that displays operational messages. The status indicator icons display
as green, yellow, or red depending on the status of the UPS.

Figure 5

shows the display screen sections.

Input

– This icon shows the state of the incoming power. It is green if the power is available and good. If it

turns yellow the voltage or frequency of the electrical power is not within acceptable limits.

Battery

– This icon shows the state of the energy storage and charge percent. Each bar of the Battery icon

represents a predefined percentage of the total energy as follows: if five bars are shown the energy charge
is between 90-100%; if four bars are shown the charge is between 70-89%; if three bars are shown the
charge is between 50-69%; if two bars are shown the charge is between 30-49%; if one bar is shown the
charge is between 10-29%; if no bars are shown the charge is 9% or less. In case the input power fails,
and the UPS goes on battery, this icon will turn yellow. When the battery is almost depleted and there are
only a few minutes of runtime left the icon will turn red.

Battery Icon

Number of Bars Displayed

Energy Charge

Five

90-100%

Four

70-89%

Three

50-69%

Two

30-49%

One

10-29%

None

9% or less

Bypass

– Under normal operation this icon should remain green. If it changes to yellow, the UPS is on

bypass and is not able to provide battery backup.

Alarm

– Under normal operation this icon should remain green. If it changes to yellow or red, there may be

an issue with the UPS. Check the UPS and its local display for details.

Operation

Summary of Contents for Remote Monitoring Device

Page 1: ...p n P 164000516 Revision 02 Installation and Operation Manual Eaton Remote Monitoring Device...

Page 2: ...rved No part of this document may be reproduced in any way without the express written approval of Eaton IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructio...

Page 3: ...e em mo ot te e M Mo on niit to or riin ng g D De ev viic ce e 1 1 Introduction 1 Installation 2 Network Card Installation 2 Network Card Configuration 3 RMD Installation 3 Operation 5 RMD Components...

Page 4: ...iv Eaton Remote Monitoring Device RMD Installation and Operation Manual P 164000516 Rev 02 Table of Contents...

Page 5: ...UPS from virtually any location within the facility up to 300 feet from the UPS It will display the general state of the UPS and key metrics like battery charge and available runtime when on battery...

Page 6: ...PXG card or Power Xpert Gateway Xslot PXGX card must be installed in the UPS to use the RMD Install the PXG card into the UPS Minislot or the PXGX card into the UPS Xslot Refer to the applicable Eato...

Page 7: ...RJ45 Ethernet connector on the RMD see Figure 4 3 Connect the Cat5 cable to the RJ45 Ethernet connector on the PXG card Refer to the applicable Eaton UPS Installation and Operation manual for the UPS...

Page 8: ...he PXG card has illuminated connect the charger cord micro USB connector to the micro USB connector on the RMD see Figure 4 Connect the transformer side of the charger cord to a 120 Vac service outlet...

Page 9: ...Figure 5 shows the display screen sections Input This icon shows the state of the incoming power It is green if the power is available and good If it turns yellow the voltage or frequency of the elec...

Page 10: ...th the PXG card S Siille en nc ciin ng g t th he e A Au ud diib blle e A Alla ar rm m To silence the audible alarm press the power button momentarily S Sy ys st te em m E Ev ve en nt ts s The followin...

Page 11: ...seconds 3 Remove and re seat the PXG card within the mini slot and waiting approximately two minutes until the Status indicator is illuminated 4 Once illuminated turn the RMD back on by re inserting t...

Page 12: ...a will display the remaining backup time in minutes and seconds Both the Input and Battery icons are illuminated yellow due to loss of input power while the UPS is on battery Figure 8 On Battery Scree...

Page 13: ...indicates the UPS has an active alarm and requires immediate attention If this occurs check the state of the UPS and if necessary contact service as the UPS may not be able to provide backup power All...

Page 14: ...y of the following Scheduling initial startup Regional locations and telephone numbers A question about any of the information in this manual A question this manual does not answer Please call the Hel...

Page 15: ...Eaton Remote Monitoring Device RMD Installation and Operation Manual P 164000516 Rev 02 11 Equipment Registration...

Page 16: ...P 16400051602 P 164000516 02...

Reviews: