Eaton Remote Monitoring Device (RMD) Installation and Operation Manual P-164000516—Rev 02
7
If the network cable is securely connected to both the PXG card and the RMD, and display on the RMD is
completely white (i.e. no communication), communication can be reattempted. To re-establish communication:
1.
Unplug the microUSB power connection from the RMD.
2.
Turn the RMD off by holding the power pushdown switch down for 11 seconds.
3.
Remove and re-seat the PXG card within the mini-slot and waiting approximately two minutes until the
Status indicator is illuminated.
4.
Once illuminated, turn the RMD back on by re-inserting the microUSB power connection into the RMD.
After 55 seconds check to see if communication has been established with between the PXG card and the
RMD.
Figure 6. Communication Error Screen
Normal Screen
– When the UPS is operating normally with full load protection, the information area will
display
System normal
and all status indicators will be illuminated green as shown in
Figure 7
.
Figure 7. Normal Screen