82
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES
MN040041EN—August 2019 www.eaton.com
Chapter 6 — PID Application
Feedforward
Table 111. Basic — P8.5.1
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P8.5.1.1
PID2 Feedforward Func
0
1400
See Par ID 1330
P8.5.1.2
PID2 Feedforward Gain
-1000.0
1000.0
%
100.0
1401
Table 112. Feedforward 1 — P8.5.2
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P8.5.2.1
PID2 Feedforward 1 Source
0
1402
0 = Not Used
1 = AI1
2 = AI2
3 = Slot A: AI1
4 = Slot B: AI1
5 = FB Process Data Input 1
6 = FB Process Data Input 2
7 = FB Process Data Input 3
8 = FB Process Data Input 4
9 = FB Process Data Input 5
10 = FB Process Data Input 6
11 = FB Process Data Input 7
12 = FB Process Data Input 8
13 = PT100 Temperture
14 = PID1 Output
15 = SlotA PT100 Temp Channel 1
16 = SlotA PT100 Temp Channel 2
17 = SlotA PT100 Temp Channel 3
18 = SlotB PT100 Temp Channel 1
19 = SlotB PT100 Temp Channel 2
20 = SlotB PT100 Temp Channel 3
21 = FB PID2 Feedforward 1
22 = FB PID2 Feedforward 2
P8.5.2.2
PID2 Feedforward 1 Min
-200.00
200.00
%
0.00
1403
P8.5.2.3
PID2 Feedforward 1 Max
-200.00
200.00
%
100.00
1404
Table 113. Feedforward 2 — P8.5.3
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P8.5.3.1
PID2 Feedforward 2 Source
0
1405
See Par ID 1402
P8.5.3.2
PID2 Feedforward 2 Min
-200.00
200.00
%
0.00
1406
P8.5.3.3
PID2 Feedforward 2 Max
-200.00
200.00
%
100.00
1407
Table 114. Fire Mode — P9
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P9.1
Fire Mode Function
0
535
0 = Closing Contact
1 = Opening Contact
P9.2
Fire Mode Ref Select Function
0
536
0 = Fire Mode Min Frequency
1 = Fire Mode Ref
2 = Fieldbus Ref
3 = AI1
4 = AI2
5 = AI1 + AI2
6 = PID1 Control Output
7 = PID2 Control Output
P9.3
Fire Mode Min Frequency
See Par ID 101
See Par ID 102
Hz
15.00
537
P9.4
Fire Mode Freq Ref 1
0.0
100.0
%
75.0
565
P9.5
Fire Mode Freq Ref 2
0.0
100.0
%
100.0
564
P9.6
Fire Mode Test Enable
2443
See Par ID 1346
P9.7
Smoke Purge Frequency
0.0
100.0
%
50.0
554
ote:
N
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.
Input function is Level sensed.