148
Appendix A—Description of parameters
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES
MN040041EN—August 2019 www.eaton.com
Code
Modbus ID
Parameter
Application
RO/RW
P2.4.8
179
AI1 Sleep Limit
3
RW
This parameter defines the sleep frequency level in the joystick control mode. The output of the drive turns
off if the joystick reference stays below the sleep limit for longer than the sleep delay time parameter
Para ID 180.
Figure 46. Example of sleep limit function
Frequency Reference
Hz
Reference
Scaling Max
P2
.
22 = 70 Hz
Max Freq
.
P1
.
2 = 50 Hz
Min Freq
.
P1
.
1 =
Ref
.
Scaling Min
P2
.
21 = 0 Hz
P2
.
3/2
.
13
= 20%
P2
.4
/2
.
1
4
= 90%
REVERSE
50%
FORWARD
50%
From Reverse to Forward
From Forward to Reverse
Analog
Input (V/mA)
(0 – 10V/20 mA)
A
B
Sleep Limit
P2
.
7/2
.
18 = 7%
Joystick Hysteresis,
P1
.
2
.
8 = 20%
START
START
STOP
STOP
P2.4.9
180
AI1 Sleep Delay
3
RW
This parameter defines the joystick sleep delay time. If the joystick reference is below the sleep limit level for
the time defined the output of the drive will shutoff and be in sleep mode. Sleep function is disabled when
this value is set to 0.
P2.4.10
133
AI1 Joystick Offset
3
RW
This parameter defines the mid point of the analog joystick control. By moving the offset in a positive or
negative direction will cause the min frequency crossing point to be move b/-50% of the analog
input scale.
P2.5.1
223
AI2 Mode
1,2,3
RW
Defines the analog input 2 source mode for current or voltage, also need to set DIP switches on control board
SW2 and 3.
0 = 0-20mA - current loop with an external supply the ground jumper is not required.
1 = 0-10V - If using the 10V supply on Terminal 1 of the drive, it will require a ground jumper from
Terminal 6 to the AI- input terminal 3.
2 = -10V to +10Vdc - Voltage loop with a +10 and a -10 volt differential supply.
Figure 47. AI2 2wire-current
OFF
2-wire Transmitter
1 10V+ 10V
supply
2
AI1+
Analog input 1+
3
AI1-
Analog input 1-
4
AI2+
Analog input 2+
5
AI2-
Analog input 2-
6 GND I/O
Ground
13
24Vo
24V auxillary voltage
Actual
Value
I = (0)4...20mA
−
+
ON
AI
AI2
Standard I/O Board
Terminal
Signal