POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES
MN040041EN—August 2019 www.eaton.com
Chapter 6 — PID Application
Table 127. BACnet MS/TP — P12.3.3
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P12.3.3.1
MSTP Baud Rate
2
594
0 = 9600
1 = 19200
2 = 38400
3 = 76800
4 = 115200
P12.3.3.2
MSTP Device Address
0
127
1
595
P12.3.3.3
MSTP Instance Number
0
4194302
Varies
596
P12.3.3.4
MSTP Comm Timeout
0
60000
ms
10000
598
P12.3.3.5
MSTP Protocol Status
599
0 = Stopped
1 = Operational
2 = Faulted
P12.3.3.6
MSTP Fault Code
600
0 = None
1 = Sole Master
P12.3.3.7
MSTP Fault Response
0
2526
See Par ID 2516
P12.3.3.8
MSTP Max Master
127
1537
EtherNet Bus
Table 128. Basic Setting — P12.4.1
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P12.4.1.1
IP Address Mode
1
1500
0 = Static IP
1 = DHCP with AutoIP
P12.4.1.2
Active IP Address
1507
P12.4.1.3
Active Subnet Mask
1509
P12.4.1.4
Active Default Gateway
1511
P12.4.1.5
MAC Address
1513
P12.4.1.6
Static IP Address
192.168.1.254
1501
P12.4.1.7
Static Subnet Mask
255.255.255.0
1503
P12.4.1.8
Static Default Gateway
192.168.1.1
1505
P12.4.1.9
Enable BACnetIP
0
1725
See Par ID 1346
Table 129. Modbus TCP — P12.4.2
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P12.4.2.1
Connection Limit
5
609
P12.4.2.2
Modbus TCP Unit ID
1
610
P12.4.2.3
Comm Timeout Modbus TCP
0
60000
ms
10000
611
P12.4.2.4
Modbus TCP Protocol Status
612
See Par ID 599
P12.4.2.5
Modbus TCP Fault Response
0
2517
See Par ID 2516
P12.4.2.6
Modbus TCP Trusted IP Enable
1
74
See Par ID 1346
P12.4.2.7
Trusted IP White List
0xC0.0xA8.
0x01.0xFF.
0x00.0x00.
0x00.0x00.
0x00.0x00.
0x00.0x00
68
ote:
N
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.
Input function is Level sensed.