46
Chapter 5—Basic application
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES
MN040041EN—August 2019 www.eaton.com
Table 42. Drive — P6.2
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P6.2.1
Line Start Lockout
2
750
0 = Disabled, No Change
1 = Enable, No Change
2 = Disabled, Changed
3 = Enable, Changed
P6.2.2
Fault Reset Start
0
2483
0 = Start/Stop After Fault Reset
1 = Restart After Fault Reset
P6.2.3
4mA Input Fault
0
306
0 = No Action
1 = Warning
2 = Warning: Previous Freq
3 = Warning: Preset Freq
4 = Fault
5 = Fault, Coast
P6.2.4
4mA Fault Frequency
0.00
See Par ID 102
Hz
0.00
331
P6.2.5
External Fault
2
307
See Par ID 308
P6.2.6
Input Phase Fault
2
332
See Par ID 308
P6.2.7
Uvolt Fault Response
2
330
See Par ID 308
P6.2.8
Unit Under Temp Prot
2
1564
See Par ID 308
P6.2.9
RTC Fault
1
955
See Par ID 308
P6.2.10
Replace Battery Fault
Response
1
1256
See Par ID 308
P6.2.11
Replace Fan Fault Response
1
1257
See Par ID 308
P6.2.12
Cold Weather Mode
0
2126
See Par ID 1679
P6.2.13
Cold Weather Volt. Level
0.0
20.0
%
2.0
2127
P6.2.14
Cold Weather Time Out
0
10
min
3
2128
P6.2.15
Cold Weather Password
2129
P6.2.16
Under Temp Fault Override
2130
See Par ID 2118
P6.2.17
STO Fault Response
2
2427
0 = No Action
1 = Warning
2 = Fault
P6.1.18
Preheat Control Source
31
2160
0 = DigIN:NormallyOpen
1 = DigIN:NormallyClose
2 = DigIN: 1
3 = DigIN: 2
4 = DigIN: 3
5 = DigIN: 4
6 = DigIN: 5
7 = DigIN: 6
8 = DigIN: 7
9 = DigIN: 8
10 = DigIN: A: IO1: 1
11 = DigIN: A: IO1: 2
12 = DigIN: A: IO1: 3
13 = DigIN: A: IO5: 1
14 = DigIN: A: IO5: 2
15 = DigIN: A: IO5: 3
16 = DigIN: A: IO5: 4
17 = DigIN: A: IO5: 5
18 = DigIN: A: IO5: 6
19 = DigIN: B: IO1: 1
20 = DigIN: B: IO1: 2
21 = DigIN: B: IO1: 3
22 = DigIN: B: IO5: 1
23 = DigIN: B: IO5: 2
24 = DigIN: B: IO5: 3
25 = DigIN: B: IO5: 4
26 = DigIN: B: IO5: 5
27 = DigIN: B: IO5: 6
31 = Drive Temperature
32 = SlotA PT100 Temp Channel 1
33 = SlotA PT100 Temp Channel 2
34 = SlotA PT100 Temp Channel 3
otes:
N
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.