![Eaton PowerXL DH1 Applications Manual Download Page 58](http://html1.mh-extra.com/html/eaton/powerxl-dh1/powerxl-dh1_applications-manual_4119853058.webp)
34
Chapter 5—Basic application
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES
MN040041EN—August 2019 www.eaton.com
Table 21. Energy Savings — M4
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
M4.1
Energy Savings
Varies
0.000
2120
Table 22. FB Monitor Menu — M5
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
M5.1
Control Board DIDO
Status
2209
Bit 0 = DIN1 Status
Bit 1 = DIN2 Status
Bit 2 = DIN3 Status
Bit 3 = DIN4 Status
Bit 4 = DIN5 Status
Bit 5 = DIN6 Status
Bit 6 = DIN7 Status
Bit 7 = DIN8 Status
Bit 8 = DO1 Status
Bit 9 = RO1 Status
Bit 10 = RO2 Status
Bit 11 = RO3 Status
Bit 12 = SlotA with board
Bit 13 = SlotB with board
Bit 14 = Virtual RO1 Status
Bit 15 = Virtual RO2 Status
M5.2
SlotA DIDO Status
2210
Bit 0 = IO1_DIN1 Status
Bit 1 = IO1_DIN2 Status
Bit 2 = IO1_DIN3 Status
Bit 3 = IO1_DO1 Status
Bit 4 = IO1_DO2 Status
Bit 5 = IO1_DO3 Status
Bit 6 = IO3_RO1 Status
Bit 7 = IO3_RO2 Status
Bit 8 = IO3_RO3 Status
Bit 9 = IO5_AC1 Status
Bit 10 = IO5_AC2 Status
Bit 11 = IO5_AC3 Status
Bit 12 = IO5_AC4 Status
Bit 13 = IO5_AC5 Status
Bit 14 = IO5_AC6 Status
M5.3
SlotB DIDO Status
2211
Bit 0 = IO1_DI1
Bit 1 = IO1_DI2
Bit 2 = IO1_DI3
Bit 3 = IO1_DO1
Bit 4 = IO1_DO2
Bit 5 = IO1_DO3
Bit 6 = IO3_RO1
Bit 7 = IO3_RO2
Bit 8 = IO3_RO3
Bit 9 = IO5_AC1
Bit 10 = IO5_AC2
Bit 11 = IO5_AC3
Bit 12 = IO5_AC4
Bit 13 = IO5_AC5
Bit 14 = IO5_AC6
Bit 15 = Not Used
M5.4
Application Status
Word
29
Bit 0 = MC_Ready
Bit 1 = MC_Run
Bit 2 = MC_Fault or Fault Trip
Bit 3 = FB_Ref_Active
Bit 4 = MC_Stopping
Bit 5 = MC_Reverse
Bit 6 = MC_Warning or AR
Bit 7 = MC_ZeroSpeed
Bit 8 = IO Control Indicator
Bit 9 = Panel Control Indicator
Bit 10 = Panel Fieldbus Control Indicator
Bit 11 = MC_DC_Brake
Bit 12 = RunEnable
Bit 13 = Run Bypass
Bit 14 = External Brake Control
Bit 15 = In Bypass Mode
ote:
N
Parameter value will be set to be default when changing macros.